Miele Indoor Fireplace MNTSVBE User Manual

INSTALLATION  
INSTRUCTIONS  
B-VENT MULTI-OPEN  
ELITE® SERIES  
This appliance may be installed in an aftermarket perma-  
nently located, manufactured home (USA only) or mobile  
home, where not prohibited by local codes. This appliance  
is only for use with the type of gas indicated on the rating  
plate. This appliance is not convertible for use with other  
gases, unless a certified kit is used.  
B-VENTED GAS FIREPLACES  
P/N 850,025M REV. B 01/2007  
MODELS  
Millivolt Models  
EBVSTNM EBVSTPM  
EBVPFNM EBVPFPM  
EBVCRNM EBVCRPM  
EBVCLNM EBVCLPM  
Electronic Models  
EBVSTNE EBVCRNE  
EBVPFNE EBVCLNE  
In the Commonwealth of Massachusetts & New York:  
Installation must be performed by a licensed plumber or  
gas fitter.  
See Table of Contents for location of additional New York  
& Commonwealth of Massachusetts requirements.  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
WARNING:IFTHEINFORMATIONINTHISMANUAL  
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-  
SION MAY RESULT CAUSING PROPERTY DAM-  
AGE, PERSONAL INJURY OR LOSS OF LIFE.  
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE  
LESINSTRUCTIONSDONNÉDANSCETTENOTICEPOUR  
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU  
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE  
BLESSURE OU LA MORT.  
FOR YOUR SAFETY: Do not store or use gasoline  
or other flammable vapors or liquids in the vicin-  
ity of this or any other appliance.  
POURVOTRESÉCURITÉ: Nepasentreposerniutiliser  
d'essencenid'autrevapeursouliquidesinflammables  
dans le voisinage de cet appareil ou de tout autre  
appareil.  
FOR YOUR SAFETY: What to do if you smell gas:  
• DO NOT light any appliance.  
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une  
• DO NOT touch any electrical switches.  
• DO NOT use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow your gas suppliers  
instructions.  
odeur de gaz:  
Ne pas tenter d'allumer d'appareil.  
Netouchezàaucuninterrupteur. Nepasvousservir  
des téléphones se trouvant dans le batiment où  
vous vous trouvez.  
Evacuez la piéce, le bâtiment ou la zone.  
Appelez immédiatement votre fournisseur de gaz  
depuis un voisin. Suivez les instructions du  
fournisseur.  
• Ifyourgassuppliercannotbereached, callthe  
fire department.  
Installation and service must be performed by a  
qualified installer, service agency or the gas  
supplier.  
Si vous ne pouvez rejoindre le fournisseur de gaz,  
appelez le service dos incendies.  
L'installationetservicedoitêtreexécutéparunqualifié  
OTL Report No. 116-F-07A-5  
installeur,agencedeserviceoulefournisseurdegaz.  
 
S'assurerquelebrùleuretlecompartimentdes  
commandes sont propres. Voir les instruc-  
tions d'installation et d'utilisation qui  
accompagnent l'appareil.  
Table 1 shows the units' gas orifice size  
for the elevations indicated.  
Maximum inlet gas supply pressure to these  
appliances is 10.5 inches water column (2.61  
kPa) for natural gas and 13.0 inches water  
column (3.23 kPa) for propane.  
Orifice size  
Model  
No.  
Elevation  
Feet (meters)  
These appliances must be isolated from the gas  
supplypipingsystem(byclosingtheirindividual  
manualshut-offvalve)duringanypressuretest-  
ing of the gas supply piping system at test  
pressures equal to or less than¹⁄₂ psig (3.5 kPa).  
Provide adequate clearances around air open-  
ings and adequate accessibility clearance for  
service and proper operation. Never obstruct  
the front, back and/or side viewing surfaces of  
the appliance.  
Nat. Prop.  
EBVST  
EBVPF  
#32  
#34  
#50  
#50  
0-4500  
(0-1372)  
EBVCR  
EBVCL  
These appliances and their individual shut-off  
valves must be disconnected from the gas supply  
piping system during any pressure testing of that  
systematpressuresinexcessof¹⁄psig(3.5kPa).  
These appliances are designed to operate on  
naturalorpropanegasonly.Theuseofotherfuels  
or combination of fuels will degrade the perfor-  
mance of this system and may be dangerous.  
Table 1  
Themillivoltappliancesaremanuallycontrolled  
and feature a spark ignitor (piezo) that allows  
theappliance'spilotgastobelitwithouttheuse  
of matches or batteries. This system will still  
function in the event of a power outage.  
These appliances must not be connected to  
a chimney or flue serving a separate solid  
fuel burning appliance.  
Millivolt Models -  
Millivolt models come standard with the  
manually-modulated gas valve; flame ap-  
pearance and heat output can be con-  
trolled at the gas valve. Input of millivolt  
models is shown in the following table:  
Carbon Monoxide Poisoning: Early signs of  
carbon monoxide poisoning are similar to  
the flu with headaches, dizziness and/or  
nausea. If you have these signs, obtain  
fresh air immediately. Turn off the gas  
supply to the appliance and have it ser-  
viced by a qualified professional, as it may  
not be operating correctly.  
Do not use these appliances if any part has  
been under water. Immediately call a quali-  
fied, professional service technician to inspect  
the appliance and to replace any parts of the  
control system and any gas control which  
have been under water.  
Millivolt Models  
Natural and Propane  
Gas Models  
EBVSTNM, EBVPFNM,  
EBVSTPM, EBVPFPM,  
EBVCLNM, EBVCRNM,  
EBVCLPM, EBVCRPM  
Input rate (BTU/H)  
Manually-modulated  
30,000 TO 37,500  
27,000 TO 34,000  
28,000 TO 34,000  
27,000 TO 34,000  
Ne pas se servir de cet appareil s'il a été plongé  
dans l'eau, complètement ou en partie. Appeler  
untechnicienqualifiépourinspecterl'appareilet  
remplacer toute partie du système de contrôle et  
toute commande qui ont été plongés dans l'eau.  
WARNING: B-VENTAPPLIANCESARENOT  
DESIGNED TO OPERATE IN NEGATIVELY  
PRESSUREDENVIRONMENTS(PRESSURE  
WITHIN THE HOME IS LESS THAN PRES-  
SURES OUTSIDE). SIGNIFICANT NEGA-  
TIVELY PRESSURED ENVIRONMENTS  
CAUSED BY WEATHER, HOME DESIGN,  
OR OTHER DEVICES MAY IMPACT THE  
OPERATION OF THESE APPLIANCES.  
NEGATIVE PRESSURES MAY RESULT IN  
POOR FLAME APPEARANCE, SOOTING,  
DAMAGE TO PROPERTY AND/OR SEVERE  
PERSONAL INJURY. DO NOT OPERATE  
THESEAPPLIANCESINNEGATIVELYPRES-  
SUREDENVIRONMENTS. PROVIDINGAD-  
EQUATE VENTILATION TO THE APPIANCE  
FORCOMBUSTIONAIRWILLELIMINATEA  
NEGATIVE PRESSURE ENVIRONMENT.  
Electronic Models -  
Electronic models have a fixed rate gas valve.  
Input of electronic models is shown in the  
following table:  
This appliance may be installed in an af-  
termarket permanently located, manufac-  
tured home (USA only) or mobile home,  
where not prohibited by local codes. This  
appliance is only for use with the type of  
gas indicated on the rating plate. This ap-  
pliance is not convertible for use with  
other gases, unless a certified kit is used.  
Electronic Models*  
Input rate (BTU/H)  
Natural Gas Models  
Fixed Rate  
EBVSTNE, EBVPFNE,  
EBVCLNE, EBVCRNE,  
37,500  
34,000  
* See page 16 for Electronic Models conversion from  
Natural gas to Propane.  
Cetappareilpeutêtreinstallédansunmaison  
préfabriquée (É.-U. seulement) ou mobile  
déjà installée à demeure si les réglements  
locaux le permettent.  
All Models -  
Maximum manifold pressure is 3.5 in. w.c.  
(0.87 kPa) for natural gas and 10 in. w.c.  
(2.49 kPa) for LP/Propane gas.  
Cet appareil doit être utilisé uniquement avec  
les types de gaz indiqués sur la plaque  
signalétique. Nepasl'utiliseravecd'autresgaz  
sauf si un kit de conversion certifié est installé.  
Installations at Altitudes of 0 to 4500 ft.-  
Units are tested and approved for elevations  
of 0 to 4500 feet (0 to 1372 meters).  
WARNING: FAILURE TO COMPLY WITH  
THEINSTALLATIONANDOPERATINGIN-  
STRUCTIONS PROVIDED IN THIS DOCU-  
MENT WILL RESULT IN AN IMPROP-  
ERLY INSTALLED AND OPERATING AP-  
PLIANCE,VOIDINGITSWARRANTY. ANY  
CHANGE TO THIS APPLIANCE AND/OR  
ITS OPERATING CONTROLS IS DANGER-  
OUS. IMPROPERINSTALLATIONORUSE  
OF THIS APPLIANCE CAN CAUSE SERI-  
OUS INJURY OR DEATH FROM FIRE,  
BURNS, EXPLOSION OR CARBON MON-  
OXIDE POISONING.  
Test gage connections are provided on the  
front of the millivolt gas control valve (iden-  
tified IN for the inlet and OUT for the mani-  
fold side). A ¹⁄₈" NPT test gage connection is  
provided at the inlet and outlet side of  
the electronic gas control valve.  
Installations at Altitudes above 4500 ft.-  
For elevations above 4500 feet (1372  
meters), install the unit according to the  
regulations of the local authorities having  
jurisdictionand,intheUSA,thelatestedition  
of the National Fuel Gas Code (ANSI Z223.1)  
or, in Canada, the latest edition of the  
CAN1-B149.1 and .2 codes.  
Minimum inlet gas pressure to these appliances  
is5.0 incheswatercolumn(1.24kPa)fornatural  
gasand11.0incheswatercolumn(2.74kPa)for  
propane for the purpose of input adjustment.  
3
 
Gas vent caps that are located 8' or more from  
a portion of a building which extends at an  
angle greater than 45° upward from the hori-  
zontal may terminate in accordance with (Fig-  
ure 3 ), provided that in no case shall any  
discharge opening on the cap be less than 2'  
(610 mm) horizontally from the roof surface  
(National Fuel Gas Code ANSI Z223.1 (NFPA  
54) 7.6.2) (CAN/CGA B149).  
TYPICAL LOCATIONS  
*When See-Through (EBST-2) is  
installed with one side flush  
with a wall,opposite wall must  
n o t e x t e n d b e y o n d e i t h e r  
viewing side of the fireplace.  
Corner - Left  
(EBCL-2)  
Corner - Right  
(EBCR-2)  
**See-Through  
(EBST-2)  
Bay  
(EBBAY)  
These instructions should be used as a  
guideline and do not supersede local codes  
in any way.  
Peninsula  
(EBPF-2)  
**When See-Through (EBST-2) is  
installed in the middle of a room,  
do not extend side walls beyond  
either viewing side of the fireplace.  
*See-Through  
(EBST-2) -  
one side flush with a wall  
Multiple Terminations These appliances  
may vent adjacent to and at the same level  
with any other gas appliances (including di-  
rect-vent appliances) provided that there is at  
least 2 ft. (0.6m) between the proximal edges  
of the vent caps. These appliances may be  
vented adjacent to a chimney vent servicing a  
solid fuel fireplace provided the B-vent cap is  
at least 2 ft. (0.6m) away from the nearest  
point of the chimney opening.  
Figure 2  
APPLIANCE AND VENT CLEARANCES  
WARNING: CHILDREN AND ADULTS  
SHOULD BE ALERTED TO THE HAZARDS  
OFHIGHSURFACETEMPERATURES.USE  
CAUTION AROUND THE APPLIANCE TO  
AVOID BURNS OR CLOTHING IGNITION.  
YOUNG CHILDREN SHOULD BE CARE-  
FULLY SUPERVISED WHEN THEY ARE IN  
THE SAME ROOM AS THE APPLIANCE.  
The appliance is approved with zero clear-  
ance to combustible materials on all sides (as  
detailed in Table 2), with the following excep-  
tion: When the unit is installed with one side  
flush with a wall, the wall on the other side of  
the unit must not extend beyond the front  
edge of the unit.  
Note: Venting terminals shall not be recessed  
into a wall or siding.  
WARNING: DO NOT PLACE CLOTHING  
OR OTHER FLAMMABLE MATERIALS  
ON OR NEAR THIS APPLIANCE.  
1/2 in. (13 mm)  
BACK  
0 in. (0 mm) spacers  
1/2 in. (13 mm)  
SIDES  
X
12  
Roof Pitch is X/12  
0 in. (0 mm) spacers  
AVERTISSEMENT: SURVEILLER LES  
ENFANTS. GARDER LES VÊTEMENTS,  
LES MEUBLES, L'ESSENCE OU AUTRES  
LIQUIDESÀ VAPEURINFLAMMABLES À  
COTE DE L'APPAREIL.  
TOP SPACERS  
FLOOR  
0 in. (0 mm)  
0 in. (0 mm)  
From Bottom  
of Unit to  
Ceiling  
Minimum Height from Roof  
to Lowest Discharge Opening  
64 in. (1626 mm)  
These appliances are equipped with an inte-  
gral combustion air door and actuator arm.  
Combustion air kits are optional.Install as  
shown in Step 6 on page 12.  
VENT  
1 in. (25.4 mm)  
Minimum Height  
from Roof to Lowest  
Discharge Opening  
SERVICE CLEARANCES  
Roof Slope  
VIEWING  
SIDES -  
(FRONT, BACK  
OR SIDE)  
LOCATION  
In selecting the location, the aesthetic and func-  
tional use of the appliance are primary concerns.  
However, vent system routing to the outside  
atmosphere and access to the fuel supply are  
alsoimportant. Considerationshouldbegivento  
trafficways,furniture,draperies,etc.,duetohigh  
surface temperatures (Figure 2 ). The location  
should also be free of electrical, plumbing or  
other heating/air conditioning ducting.  
3 Feet. (0.9 meters)  
Feet  
1' 0"  
2' 0"  
4' 0"  
6' 0"  
8' 0"  
Meters  
0.3  
Flat to 6/12  
Over 7/12 to 9/12  
Over 10/12 to 12/12  
Over 13/12 to 16/12  
Over 17/12 to 21/12  
0.6  
Table 2  
1.2  
1.8  
In addition, when the unit is installed in the  
middle of a room, the side walls surrounding  
the unit must not extend beyond the front or  
rear edge of the unit. See Figure 2.  
2.4  
Figure 3  
The appliance should be mounted on a fully  
supported base extending the full width and  
depth of the unit. The appliance may be located  
on or near conventional construction materi-  
als. However, if installed on combustible mate-  
rials, such as carpeting, vinyl tile, etc., a metal  
or wood barrier covering the entire bottom  
surface must be used.  
Vertical Vent Termination Clearances  
TYPICAL INSTALLATION SEQUENCE  
The typical sequence of installation follows,  
however,eachinstallationisuniqueresultingin  
variations to those described.  
Gas Vent Rule Gas vent caps are not permit-  
ted within 8 feet (2.4 mm) of a vertical wall or  
similar obstruction.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
4
 
See the page numbers references in the follow-  
ing steps for detailed procedures.  
If the appliance is to be elevated above floor  
level, a solid continuous platform must be  
constructed. Headers may be in direct contact  
with the appliance top spacers but must not be  
supported by them or notched to fit around  
them. All construction above the appliance  
must be self supporting, DO NOT use the  
appliance for structural support.  
Top Radiant  
Panel  
Step 1. (page 5) Construct the appliance  
framing. Position the appliance within the  
framing and secure with nailing brackets.  
Step 2. (page 5) Route gas supply line to  
appliance location.  
Top Bustle  
Bottom  
Bustle  
Control  
Compartment  
Access Panel  
Step 3. (page 5) Install the vent system  
and exterior termination.  
Step 4. (page 10) Field Wiring  
a. Millivolt Appliances The operating con-  
trol switch is factory installed.  
b. Electronic Appliances Connect 120 Vac  
electrical power to the appliance receptacle.  
Step 5. (page 11) Make connection to gas  
supply.  
Step 6. (page 12) OutsideAirKitInstallation  
Step 7. (page 13) Install the log set, ver-  
miculite and glowing embers.  
Step 8. (page 13) Checkout appliance op-  
eration.  
Step 9. (page 13) Install glass enclosure  
panels.  
Step 10. (page 14) Burner Adjustment.  
Step 11. (page 14) Spillage Test and Safety  
Limit Switch Operation.  
Unit Parts Identification  
Side Nailing Flanges  
Figure 4  
Thefireplaceshouldbesecuredtotheframingat  
the side(s) and/or rear of the unit using the  
factory-provided nailing flanges. Install the nail-  
ing flanges - 8 (EBVST), 4 (EBVPF, EBVCL,  
EBVCR)-asshowninFigure5usingtheexisting  
screws. Position the fireplace within the fram-  
ing. When required, the flanges may be bent 90  
degrees by hand or with the assistance of a  
hammer. Use woodscrewstosecurethenailing  
flangestotheframing.SeeTable2onpage4for  
clearances of framing members to cabinet parts  
in the nailing flange area. The nailing flange itself  
is exempt from these clearances.  
3- Open the control compartment access  
panel, by actuating the spring-loaded mag-  
netic catches securing the panel, gently de-  
pressing the outer top corners of the panel  
until the catches "pop" the panel free and  
allowingittoswingoutanddowntoopen. See  
Figure 20 on page 12.  
4 - Open the latches (located on the left and  
right sides of the unit front opening, under the  
fireboxfloor)securingtheglassenclosurepanel.  
Remove the panel by tilting it outward at the  
bottom and lifting it up. Set the door aside  
protecting it from inadvertent damage. See  
Figure 24 on page 13.  
Floor Nailing Tabs  
Secure the fireplace to the floor as shown in  
Figure 5.  
Step 12. (page 15) Install the hoods.  
Step 1. FRAMING  
Step 2. ROUTING GAS LINE  
DETAILED INSTALLATION STEPS  
Route a ¹⁄₂" (13 mm) gas line as shown in  
Figures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or  
11 (EBVCR) on pages 6 and 7. Gas lines must  
be routed, constructed and made of materials  
that are in strict accordance with local codes  
and regulations.  
Frame these appliances as illustrated in Fig-  
ures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or  
11 (EBVCR) on pages 6 and 7. All framing  
details must allow for a minimum clearance  
to combustible framing members as shown  
inTable 2 on page 4.  
The appliance is shipped with all gas controls  
and components installed and pre-wired.  
1 - Remove the shipping carton.  
2 - Removethetopradiantpanel;seeFigure4.  
All appliances are factory-equipped with a flex-  
iblegaslineconnectorand¹⁄inchshutoffvalve.  
(See step 5 on page 11).  
EBVST SHOWN  
EBVCL SHOWN  
(FOR EBVCR VIEW, INTERCHANGE SIDES)  
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)  
Remove these two screws and use them  
when installing the nailing flanges.  
Step 3. Install the Vent System &  
Exterior Termination -  
In the United States, vent installation must  
conform with local building codes. In the ab-  
senceoflocalcodes,ventsmustbeinstalledin  
accordance with the current edition of the  
National Fuel Gas Code (ANSI-Z223.1).  
In Canada, vent installation must conform  
with local building codes. In the absence of  
local codes, vents must be installed in ac-  
cordance with the current edition of the Na-  
tional Standard of Canada CAN/CGA-B149.1  
or B149.2 Installation Code.  
Nailing  
Flanges  
Turn tabs down and secure to the floor with  
8d nails or other appropriate fasteners on all sides  
of the unit which do not have viewing glass panels.  
This gas fireplace must be vertically vented  
using listed 6 in. type-B, double-walled vent  
pipe and a listed vent termination.  
Figure 5  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
5
 
Slip the first 6 inch (152 mm) section of B-  
Vent over the fireplace flue outlet and secure  
with four sheetmetal screws (# 8 or larger),  
and install the remainder of the B-Vent to the  
outside. Minimum overall height of the vent  
system and appliance must be 10' (2.54 m)  
vertical - no offset (see Figure 6 ); or 12' (3.7  
m) when an offset up to 60 degrees from the  
vertical is used - this offset may start at the  
fireplace flue collar (see Figure 7 ). The  
maximum overall height of the vent system  
and appliance should not exceed 40 feet.  
60 degrees  
max.  
10 ft.  
12 ft.  
Minimum  
Minimum  
Install the B-vent system in accordance with  
the vent manufacturer's instructions.  
CAUTION: THIS APPLIANCE CANNOT BE  
VENTED HORIZONTALLY.  
Note: Refer to the vent manufacturers in-  
stallation instructions for variations of vent-  
ing techniques. If common venting of sev-  
eral units is contemplated, it should be dis-  
cussed with an architect and the local Build-  
ing Department.  
Figure 6  
Figure 7  
Do not place insulation materials within 1 in.  
of the gas vent system.  
FIREPLACE FRAMING SPECIFICATIONS  
EBVST  
(See-Through)  
EBVPF  
(Peninsula)  
Minimum Framing  
Stud size is 2 x 4  
Minimum Framing  
Stud size is 2 x 4  
inches (millimeters)  
inches (millimeters)  
Gas Line  
Center of gas line  
is 3 in. (76 mm)  
up from floor.  
Gas Line  
Center of gas line  
is 3 in. (76 mm)  
up from floor.  
6¹⁄₄  
(159)  
6¹⁄₄  
(159)  
*41¹⁄₂  
(1054)  
*41¹⁄₂  
(1054)  
22³⁄₄**  
(578)  
22³⁄₄**  
(578)  
40¹⁄₈  
(1019)  
41¹⁄₂  
(1054)  
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)  
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits  
easier fireplace installation, if unit is installed after framing is erected.)  
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)  
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits  
easier fireplace installation, if unit is installed after framing is erected.)  
**Based on 5/8drywall. Use 23for 1/2drywall.  
**Based on 5/8drywall. Use 23for 1/2drywall.  
Figure 8  
Figure 9  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
6
 
FIREPLACE FRAMING SPECIFICATIONS CONTINUED  
EBVCL (Corner-Left)  
Minimum Framing  
Stud size is 2 x 4  
EBVCR (Corner-Right)  
Minimum Framing  
Stud size is 2 x 4  
inches (millimeters)  
inches (millimeters)  
Gas Line  
Center of gas line  
is 3 in. (76 mm)  
up from floor.  
*41¹⁄₂  
(1054)  
Gas Line  
*41¹⁄₂  
(1054)  
Center of gas line  
is 3 in. (76 mm)  
up from floor.  
9³⁄₄  
(248)  
6¹⁄₄  
(159)  
40¹⁄₈  
(1019)  
40¹⁄₈  
(1019)  
9⁷⁄₈  
(251)  
Optional Gas Line  
Location Center of gas line  
is 3 in. (76 mm) up from floor.  
24  
(610)  
24  
(610)  
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)  
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier  
fireplace installation, if unit is installed after framing is erected.)  
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)  
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension  
permits easier fireplace installation, if unit is installed after framing is erected.)  
Figure 11  
Figure 10  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
7
 
FIREPLACE SPECIFICATIONS  
20¹⁄₁₆  
(510)  
FINISH WALL BRACKET  
(Front and back edge of unit top)  
EBVST (See-Through)  
Figure 12  
12 (305)  
B
A
1/2  
(13)  
FRAMING SPACERS  
(Top and Both Sides)  
A - 6 (152) DIA. FLUE OUTLET  
B - 8 (203) DIA. FLUE COLLAR  
DETAIL OF  
FINISH WALL BRACKET  
40¹⁄₈  
(1019)  
TOP VIEW  
2³⁄₄  
(70)  
¹⁄₂ (13)  
¹⁄₂ (13)  
24  
(610)  
40¹⁄₈  
(1019)  
12  
(305)  
4 (102)  
OUTSIDE AIR  
SHUTTER  
41  
(1041)  
ELECTRICAL  
INLETS  
37  
(940)  
ELECTRICAL  
INLETS  
GAS INLET  
3 (76)  
GAS INLET  
4⁹⁄₁₆  
(116)  
4⁹⁄₁₆  
(116)  
3 (76)  
6⁷⁄₈  
(175)  
6⁷⁄₈  
CONTROL  
COMPARTMENT  
ACCESS PANEL  
(175)  
FRONT VIEW  
LEFT SIDE VIEW  
RIGHT SIDE VIEW  
20¹⁄₁₆  
(510)  
FINISH WALL BRACKET  
(Front, back, and left edge of unit top)  
FRAMING SPACERS  
(Top and Side)  
EBVPF (Peninsula)  
A - 6 (152) DIA. FLUE OUTLET  
B - 8 (203) DIA. FLUE COLLAR  
12 (305)  
Figure 13  
B
A
DETAIL OF  
FINISH WALL BRACKET  
¹⁄₂  
(13)  
¹⁄₂  
(13)  
40¹⁄₈  
(1019)  
TOP VIEW  
2³⁄₄  
(70)  
24  
(610)  
12  
(305)  
4 (102)  
OUTSIDE AIR  
SHUTTER  
41  
37  
(1041)  
(940)  
ELECTRICAL  
INLETS  
GAS INLET  
4⁹⁄₁₆  
(116)  
3 (76)  
CONTROL COMPARTMENT  
ACCESS PANEL  
6⁷⁄₈  
(175)  
LEFT SIDE VIEW  
FRONT VIEW  
RIGHT SIDE VIEW  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
8
 
FIREPLACE SPECIFICATIONS CONTINUED  
20¹⁄₁₆  
(510)  
EBVCL (Corner-Left)  
Figure 14  
A - 6 (152) DIA. FLUE OUTLET  
B - 8 (203) DIA. FLUE COLLAR  
12 (305)  
B
A
DETAIL OF  
FINISH WALL BRACKET  
FINISH WALL BRACKET  
(Front and left edge of unit top)  
¹⁄₂  
(13)  
FRAMING SPACERS  
(Top, Side and Back)  
40¹⁄₈  
(1019)  
¹⁄₂  
(13)  
TOP VIEW  
2³⁄₄  
(70)  
¹⁄₂  
(13)  
12  
(305)  
24  
(610)  
4 (102)  
OUTSIDE AIR  
SHUTTER  
37  
(940)  
41  
(1041)  
ELECTRICAL  
INLETS  
GAS INLET  
4⁹⁄₁₆  
(116)  
3 (76)  
CONTROL COMPARTMENT  
ACCESS PANEL  
6⁷⁄₈  
(175)  
LEFT SIDE VIEW  
FRONT VIEW  
RIGHT SIDE VIEW  
20¹⁄₁₆  
(510)  
TOP VIEW  
EBVCR (Corner-Right)  
Figure 15  
A - 6 (152) DIA. FLUE OUTLET  
B - 8 (203) DIA. FLUE COLLAR  
12 (305)  
B
A
DETAIL OF  
FINISH WALL BRACKET  
FRAMING SPACERS  
(Top, Side and Back)  
FINISH WALL BRACKET  
(Front and right edge of unit top)  
¹⁄₂  
(13)  
40¹⁄₈  
(1019)  
2³⁄₄  
(70)  
¹⁄₂  
24  
(610)  
12  
(305)  
(13)  
4 (102)  
41  
(1041)  
OUTSIDE AIR  
SHUTTER  
37  
(940)  
ELECTRICAL  
INLETS  
GAS INLET  
3 (76)  
6⁷⁄₈  
(175)  
CONTROL COMPARTMENT  
ACCESS PANEL  
RIGHT SIDE VIEW  
FRONT VIEW  
LEFT SIDE VIEW  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
9
 
3. Remove the bottom control compartment  
access panel by compressing the spring-  
loaded hinge pin on the left side until it  
disengages from the left cabinet panel  
hole. Pull the panel away from the fire-  
place. See Figure 20 on page 12.  
Step 4. FIELD WIRING  
Millivolt Wiring Diagram  
If any of the original wire as supplied must be replaced,  
it must be replaced with Type AWM 105°C 18 GA. wire.  
Refer to Section A for millivolt appliances and  
Section B for electronic appliances. The gas  
valve is set in place and pre-wired at the  
factory on both models.  
White  
4. Remove the modesty panel by pulling the  
bottom edge of the modesty panel out of  
the locking slots of the cabinet bottom.  
Then tilt the top edge at a 45° angel and  
lift out. Remove the modesty panel care-  
fully, so that none of the wires become  
loose or disconnected.  
5. Remove the outlet receptacle by remov-  
ing the two securing screws. See Figure  
17. (The left and right designations used  
here are reversed in EBVCR applications.)  
6. Install a field-provided strain relief in the  
cabinet knockout opening for the protec-  
tion of the power supply wires.  
A. Millivolt Wiring (See Figure 16 )  
Thermopile  
1. Appliance-mounted ON/OFF burner control  
switch (rocker switch) is factory installed in  
the modesty panel. Optional wall-mounted  
switch, thermostat, or one of the optional  
remote control kits may also be used.  
2. If wall-mounted ON/OFF control or thermo-  
stat is selected, mount it in a convenient  
location on a wall near the fireplace.  
Black  
Field Wired  
Factory Wired  
APPLIANCE-MOUNTED ON/OFF SWITCH  
*OPTIONAL WALL-MOUNTED ON/OFF  
SWITCH OR OPTIONAL THERMOSTAT  
OR OPTIONAL REMOTE RECEIVER  
*Turn the appliance-mounted ON/OFF burner control  
switch to the OFF position if an optional  
control switch is installed.  
3. Wire the control switch within the millivolt  
control circuit using the 15 feet of 2 con-  
ductor wire supplied with the unit.  
Schematic Representation Only  
7. Connect the power supply wires to the  
receptacle as shown in Figure 18 on  
page 11.  
Figure 16  
Note: The supplied 15 feet of 2 conductor  
wire has one end of each conductor con-  
nected to the gas valve circuit and the other  
end of each conductor placed loose inside  
the lower compartment of the unit.  
B. Electronic Wiring  
(also see Figure 18 on page 11 )  
8. Connect the ground supply wire and the  
green wire attached to the outlet  
receptacle's green ground screw.  
9. Appliance-mounted ON/OFF burner con-  
trol switch (rocker switch) is factory in-  
stalled in the modesty panel. Optional  
wall-mounted switch, thermostat, or one  
of the optional remote control kits may  
also be used.  
Note: The electronic appliance must be con-  
nected to the main power supply.  
Caution: do not connect the optional wall  
switch to a 120V power supply.  
1. Route a 3-wire 120Vac 60Hz 1ph power  
supply to the appliance junction box.  
2. Open the control compartment access  
panel, by actuating the spring-loaded  
magnetic catches securing the panel,  
gently depressing the outer top corners  
of the panel until the catches "pop" the  
panel free and allowing it to swing out  
and down to open.  
4. If an optional control switch is installed,  
turntheappliance-mountedON/OFFburner  
control switch to the OFF position.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
10  
 
10. Ifwall-mountedON/OFFswitchorthermo-  
stat is to be used, mount it in a convenient  
location on a wall near the fireplace.  
11. If the wall-mounted ON/OFF switch is to be  
used, wire it to the the low voltage circuit  
as shown in Figure 18.  
Electronic Wiring Diagram (Honeywell)  
FIREBOX BOTTOM  
JUNCTION BOX  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA.  
wire.  
OUTLET RECEPTACLE  
CABINET  
RIGHT SIDE  
PANEL  
2. 120V, 60Hz Less than 3 amps.  
*Leave the ON/OFF switch, which is integral  
with the gas valve, in the ON position.  
*ON/OFF Switch (Integral  
with Gas Valve)  
Gas Valve  
PILOT  
ASSEMBLY  
Note: The supplied 15 feet of 2 conductor wire  
has one end of each conductor connected to  
the gas valve circuit and the other end of each  
conductor placed loose inside the lower com-  
partment of the unit.  
BK  
R
Green  
BL  
White  
Black  
Ground - Green  
Neutral - White  
120 VAC - Black  
Junction Box  
Tab Intact  
Ta b  
Broken  
12. After wiring is complete, reinstall the out-  
let receptacle; install the field-provided  
the metal junction box cover plate; rein-  
stall the modesty panel.  
Red  
Optional  
Accessory  
Switch  
Green  
Ground  
Screw  
Hot  
Neutral  
Side of  
Receptacle  
Side of  
Receptacle  
W
Transf.  
120 V.  
B
G
OUTLET RECEPTACLE  
BOX SECURING SCREW  
Note:ThegasvalveON/OFFswitchisshownin  
Figure 18. It is integral with the gas valve and  
should be set to the ON position.  
24 V  
BL  
EBST-2, EBPF-2  
R
AND EBCL-2 OUTLET RECEPTACLE SHOWN.  
EBCR-2 HAS THE OUTLET RECEPTACLE LOCATED IN  
THE LEFT CORNER OF THE UNIT  
WT  
BK  
WT  
EBBAY OUTLET RECEPTACLE LOCATED IN  
THE REAR LEFT CORNER OF THE UNIT  
IMPORTANT: Ground supply wire must  
be connected to the green wire attached  
to the outlet receptacle's green ground  
screw. See Figure 18. Failure to do so  
will result in a potential safety hazard.  
The appliance must be electrically  
grounded in accordance with local codes  
or, in the absence of local codes, the  
National Electrical Code, ANSI/NFPA 70-  
(latest edition). (In Canada, the current  
CSA C22-1 Canadian Electrical Code.)  
LIMIT SWITCH  
**OPTIONAL WALL SWITCH  
OR OPTIONAL THERMOSTAT  
OR OPTIONAL REMOTE  
RECEIVER  
VIEW OF RIGHT BOTTOM CORNER OF UNIT  
APPLIANCE-MOUNTED ON/OFF SWITCH  
**Turn the appliance-mounted ON/OFF burner control switch to  
the OFF position if an optional control switch is installed.  
OUTLET RECEPTACLE INSTALLATION  
Figure 17  
Factory Wired  
Field Wired  
Schematic Representation Only  
Figure 18  
Step 5. CONNECTING GAS LINE  
Make gas line connections. All codes require a  
shut-off valve mounted in the supply line.  
Figure 19 on page 12 illustrates two methods  
for connecting the gas supply. The flex-line  
method is acceptable in the U.S., however,  
Canadian requirements vary depending on lo-  
cality. Installation must be in compliance with  
local codes.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
11  
 
Step6. OutsideAirKitsOptional outsidemake-  
up air kits, Model FOAK-4 or FAOK-4LD, may be  
used with these appliances. Refer to the installa-  
tion instructions packaged with the air kits for  
specific installation information. If used, the out-  
side air kit must be installed before the fireplace is  
framed and enclosed in the finished wall.  
Gas Flex Line Connector  
Gas  
Valve  
³ꢀ₈" NPT ₂ ³ꢀ₈  
Flare Fitting  
¹ꢀ₂" x³ꢀ₈" Flare  
Shut-Off Valve  
³ꢀ₈ Flex Tubing  
Outside air drawn into the fireplace supplies  
air to the fire for combustion. Only one outside  
air duct is necessary, if installed. See the  
Figures on pages 8, 9 and 10 for the location  
of the units outside air inlet.  
Gas Stub  
³ꢀ₈" Nipple  
³ꢀ₈"Union  
³ꢀ₈" Close Nipple  
³ꢀ₈" Shut-Off Valve  
If additional length of duct is necessary, pur-  
chase locally available U.L. Class 0 or Class 1  
metallic ducting. The duct may extend up to 50'  
(15.24 m) in any direction.  
¹ꢀ₂  
x
³ꢀ"  
Reducer  
Figure 19 - GAS CONNECTION  
These appliances are equipped with a gas flex  
lineforuse(wherepermitted)inconnectingthe  
unit to the gas line. A gas flex line is provided to  
aid in attaching the B-vent appliance to the gas  
supply.Thegasflexlinecanonlybeusedwhere  
local codes permit. See Figure 19 for flex line  
description. The flex line is rated for both natu-  
ral and propane gas. A manual shut off valve is  
also provided with the flex line.  
Note: When installing the air duct vertically,  
DO NOT terminate the duct closer than 3'  
below the chimney top.  
Outside combustion air ducting may be run  
upwards or vertically through framing and  
ceiling joists, with the hood installed through  
an outside wall and 3' (1 m) below the termi-  
nation. Ducting may also be run downward  
through floor Joists and under the home to a  
ventilated crawlspace not considered part of  
the living area of the home.  
The gas control valve is located in the lower  
control compartment. To access the valve  
proceed as follows:  
Gas Valve  
Hinge  
Pin  
Control  
Compartment  
Access panel  
ON/OFF  
Switch  
Note: Do not terminate outside air kit in attic  
space under any circumstances.  
1- Openthecontrolcompartmentaccesspanel,  
(Figure 20 ) by actuating the spring-loaded  
magnetic catches securing the panel, gently  
depressingtheoutertopcornersofthepanel  
until the catches "pop" the panel free and  
allowing it to swing out and down to open.  
2- Remove the bottom control compartment  
access panel by compressing the spring-  
loaded hinge pin on the left side until it  
disengagesfromtheleftcabinetpanel hole.  
Pull the panel away from the fireplace. See  
Figure 20.  
Piezo  
Ignitor  
Modesty Panel  
Lock Slot  
Modesty  
Panel  
CAUTION: NEVER LOCATE INLET WHERE IT  
CAN BE BLOCKED BY SHRUBS, SNOW  
DRIFTS, ETC. NEVER LOCATE INLET IN GA-  
RAGE OR ANY AREA WHERE THERE IS AN-  
OTHERFUELBURNINGAPPLIANCEORPROD-  
UCTSEMITTINGCOMBUSTIBLEGASESSUCH  
AS PAINT, GASOLINE, ETC. IN COLD CLI-  
MATES, IT IS RECOMMENDED THE COMBUS-  
TION AIR DUCT BE INSULATED.  
Figure 20  
Turn on gas supply and test for gas leaks using  
a soapy water solution. Never use an open  
flame to check for leaks.  
A. Mix a 50% dish soap, 50% water solution.  
3- Remove the modesty panel by pulling the  
bottom edge of the modesty panel out of  
the locking slots of the cabinet bottom.  
Then tilt the top edge at a 45° angel and  
lift out. Remove the modesty panel care-  
fully, so that none of the wires become  
loose or disconnected.  
After completing the installation of the op-  
tional outside air vent system, the outside air  
control lever must be put in service and tested  
to ensure proper operation before completing  
any enclosure around the firebox. Failure to  
do so may result in extensive and costly re-  
work. Before the operation of the vent system  
can be tested, the lever securing screw must  
be removed. See Figure 21 on page 13.  
B. Light the appliance (refer to the lighting  
instructionsprovidedintheHomeowner'sCare  
and Operation Instructions).  
C. Brush all joints and connections with the  
soapy water solution to check for leaks. If  
bubbles are formed, or gas odor is detected,  
turn the gas control knob to the OFFposi-  
tion. Either tighten or refasten the leaking  
connection and retest as described above.  
The millivolt control valve has a ³⁄₈"  
(10 mm) NPT thread inlet port. The electronic  
control valve has a ¹⁄₂" (13 mm) NPT thread inlet  
port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x  
10 mm) NPT fitting.  
The hand operated outside air control lever is  
located on the right side (EBVST, EBVPF, and  
EBVCL) or left side (EBVCR) of the fireplace  
opening. See Figure 21 on page 13.  
D. When the gas lines are tested and leak free,  
observe the individual tongues of flame on the  
burner. Make sure all ports are open and  
producing flame evenly across the burner. If  
any ports are blocked, or partially blocked,  
clean out the ports.  
Secure all joints tightly using appropriate  
tools and sealing compounds (ensure pro-  
pane resistant compounds are used in pro-  
pane applications).  
To open the outside air shutter, open the bottom  
controlaccesspanel,reachintothegapbetween  
the firebox bottom and the modesty panel, and  
pull the outside air control lever all the way out.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
12  
 
Theoutsideairshuttershouldbefullyopenwhen  
the fireplace is in use and completely closed  
when the fireplace is not being used. Closing it  
whennotinusewillpreventoutsidecoldairfrom  
entering the dwelling.  
When first lighting the appliance, it will take  
a few minutes for the line to purge itself of  
air. Once purging is complete, the pilot and  
burner will light and operate as indicated in  
the instruction manual. Subsequent lightings  
of the appliance will not require such purg-  
ing. Inspect the pilot flame (remove logs, if  
necessary, handling carefully).  
Step 9. INSTALLING GLASS ENCLOSURE  
PANELS  
1. Visually inspect the gasket on the backside  
of the panels. The gasket surface must be  
clean, free of irregularities and seated firmly.  
2. Position the glass enclosure panel in front  
of the firebox opening at a 45 degree angle and  
engage the top flange over the lip at the top of  
the firebox opening. See Figure 24.  
Outside Air Control Lever with Stop Behind  
Securing Screw  
Millivolt Appliance Checkout  
3. Swing the glass enclosure panel down and  
back. Ensure the gasket seats evenly as the  
panel draws shut. Engage the Vee-flanges at  
the bottom of the panel with the latches; then  
close the latches to secure the panel.  
4. After installing the front glass enclosure  
panel, reinstall the bottom control compart-  
ment access panel by inserting the right side  
locating pin into the right side cabinet panel  
and then the left side spring-loaded pin into  
the left side cabinet panel.  
The pilot flame should be steady and, not lifting  
or floating. Flame should be blue in color with  
traces of orange at the outer edge.  
The top ³⁄₈" (10 mm) at the pilot generator  
(thermopile) and the top ¹⁄₈" min (tip) of the  
quick drop out thermocouple should be en-  
gulfed in the pilot flame. The flame should  
project 1" (25 mm) beyond the hood at all three  
ports (Figure 22).  
Outside Air Shutter in the  
Closed Position  
Replace logs after pilot inspection.  
Control Compartment Access Panel  
Outside Air Control Lever  
and Securing Screw Location  
Lower Compartment Door and Hinge  
To light the burner; turn ONthe modesty  
panel mounted ON/OFF switch and rotate the  
gas valve control knob counterclockwise to  
the ONposition.  
Top Flange  
(Glass Enclosure  
Panel Frame)  
Modesty Panel  
(EBVST, EBVPF and EBVCR Units Shown)  
Figure 21  
Front Glass  
Enclosure Panel  
Operate the actuator through several cycles  
including the closed position. Ensuring proper  
operation and freedom of movement. Return  
the actuator arm to the closed position.  
Ignitor Rod  
Hood  
MILLIVOLT  
Thermocouple  
Step7.INSTALLINGLOGS,VERMICULITE,  
DECORATIVE VOLCANIC STONE AND  
GLOWING EMBERS  
³⁄₈" Min  
(9 mm)  
Pilot  
Nozzels  
The log set is located within the firebox. One  
plastic bag of glowing embers, one plastic bag  
of decorative volcanic stone and one bag of  
vermiculate, is located in the bottom compart-  
ment. Refer to the Log Placement Guide for  
detailed placement instructions for the log set  
and glowing embers. See the Homeowners  
Manual for placement instructions of vermicu-  
late, decorative volcanic stone and rockwool.  
Thermopile  
Figure 22  
Glass  
Enclosure  
Panel  
Electronic Appliance Checkout  
Bottom Vee-flanges  
Latch  
To light the burner, turn ONthe modesty  
panelmountedON/OFFswitch andturnthegas  
control switch to the ONposition. Ensure the  
ignitor lights the pilot. The pilot flame should  
engulf the flame rod as shown in Figure 23.  
Firebox  
Floor  
(Glass Enclosure  
Panel Frame)  
EBVST SHOWN  
Figure 24 -  
Step 8. CHECKINGAPPLIANCEOPERATION  
Installing the Glass Enclosure Panel  
ELECTRONIC  
With gas line installed run initial system check-  
out before closing up the front of the unit.  
Follow the pilot lighting instructions provided  
in the Homeowner's Care and Operation In-  
structions.ForpiezoignitorlocationseeFigure  
20 on page 12 (millivolt appliances only).  
3/8 To 1/2 Inch  
Proper Flame  
(9 mm to 13 mm)  
Adjustment  
WARNING: HANDLE THE GLASS WITH  
EXTREME CARE! TEMPERED GLASS IS  
SUSCEPTIBLETODAMAGE(SCRATCHES,  
FOR EXAMPLE) HANDLE GLASS DOOR  
(GLASS ENCLOSURE PANEL) GENTLY  
WHILE REINSTALLING IT.  
Pilot  
Nozzle  
Ground  
Electrode  
Note: Lighting instructions may also be found  
on the pull out lighting instruction labels  
attached to the gas control valve.  
Flame Rod  
Hot Surface  
Igniter  
WARNING: NEVER OPERATE THE APPLI-  
ANCE WITHOUT THE FRONT GLASS EN-  
CLOSURE PANEL IN PLACE AND SECURE.  
To access the label, see the procedure on the  
previous page described for accessing the gas  
control valve.  
Figure 23  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
13  
 
Step 10. BURNER ADJUSTMENTS  
Manually-Reset Safety Limit Switch  
This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to Figure 26  
for its location. If, during appliance operation, the flame goes out (independently of the burner on/  
off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance  
to cool, then reset the safety switch by pushing the red reset button on the back of the switch.  
Note - The air shutter for the burner primary air  
openingisfactory-set. Donotadjustthefactory-  
setposition. Thefactory-setpositionisshownin  
Figure 25.  
To access the blocked flue safety limit switch refer to Figure 26:  
*Air Shutter  
Opening  
Burner  
Venturi  
Tube  
A - To access the blocked flue safety switch when top radiant panel is not covered with non-  
combustible material:  
1 - Lift up and remove top radiant panel/eyebrow assembly on the control side of unit.  
2 - Reach between the cabinet side and the firebox side wall and locate the blocked flue safety  
switch.  
Orifice  
3 - Push the red reset button on the switch.  
The applilance should then relight and remain lit. If this does not occur, turn off the appliance and  
call a qualified service technician.  
Millivolt Shown  
B - To access the blocked flue safety switch when top radiant panel is covered with non-  
combustible material:  
*Note - Do Not Adjust the Factory-Set Position.  
Theshutteropeningisshowninthetable  
below.  
NOTE - This procedure should only be performed by a qualified service technician.  
Important - Turn electrical power off before beginning this procedure.  
MAIN BURNER  
FACTORY SHUTTER SETTING  
1 - Lower bottom hinged panel on the control side of the fireplace. Remove the modesty panel  
and glass enclosure panel as described on page 5, Steps 3, 4, 5 and 6 under "Detailed Installation  
Steps" heading.  
2 - Remove the side baffle securing screws (5) and then remove the baffle.  
3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly  
through the side panel slot.  
4 - Push the red reset button on the switch.  
5 - Reinstall the switch/bracket assembly.  
6 - Reinstall the side baffle.  
Propane  
Gas  
inches  
(mm)  
Natural Gas  
inches  
(mm)  
Models  
EBVST  
EBVPF  
EBVCR  
EBVCL  
1/16 (1.5)  
7/16 (11)  
7 - Reinstall front glass door.  
8 - Raise the bottom hinged panel.  
Figure 25  
The appliance should then relight and remain lit. If this does not occur, check unit for a blocked  
flue condition.  
Step 11. Spillage Test and Safety Limit  
Switch Operation  
Spillage Test  
SAFETY SWITCH LOCATION (EBVCL SHOWN) EBVST and EBVPF Safety Switch Location Also as Shown;  
EBVCR Location on the Left End of the Fireplace.  
After appliance installation, perform this spillage  
test to verify that proper venting conditions exist:  
1 - Place unit in its normally-operated con-  
dition, that is, with the glass enclosure pan-  
els in place.  
FIREBOX SIDE BAFFLE SECURING SCREW  
FIREBOX SIDE BAFFLE  
MANUALLY-RESET  
2 - Close all doors and windows in the  
room. Turn on all exhaust fans in the house.  
3 - Light the appliance.  
SAFETY LIMIT SWITCH  
FIREBOX  
SIDE WALL  
4 - Wait 15 minutes.  
5 - To check for venting action, start by  
holding a smoke producing device within an  
inch of one edge (side edge, not top or  
bottom edge) of one glass enclosure panel.  
The smoke should be drawn toward the edge  
of the glass enclosure panel. Continue the  
test by moving the smoke producing device  
along the entire length of both side-edges of  
the glass door. Repeat the test for all glass  
enclosure panels.  
TOP RADIANT PANEL  
AND EYEBROW  
BRACKET  
SECURING SCREW  
SAFETY SWITCH  
6 - If the smoke is not drawn towards the  
edges of the glass door turn off the appli-  
anceandcallaqualifiedservicetechnican.  
CABINET  
SIDE WALL  
Figure 26  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
14  
 
Step 12. HOOD INSTALLATION  
COLD CLIMATE INSULATION  
All of these appliances must have hoods installed prior to operating on all sides with glass  
enclosure panels.  
For cold climate installations, seal all cracks  
around your appliance with noncombustible  
material and wherever cold air could enter the  
room. It is especially important to insulate  
outside chase cavity between studs and under  
floor on which appliance rests, if floor is above  
ground level. Gas line holes and other open-  
ings should be caulked or stuffed with unfaced  
fiberglass insulation. In cold climates, if the  
fireplace is being installed on a cement slab, a  
sheet of plywood or other raised platform can  
be placed underneath to prevent conducting  
coldupintotheroom. Italsohelpstosheetrock  
inside surfaces and tape for maximum air  
tightness and caulk firestops.  
On all clean face units, slide the hoods into the slots on the lower edges of the radiant panels (Figure 28).  
FINISHING REQUIREMENTS  
Wall Details  
Complete finished interior wall. To install the appliance facing flush with the finished wall, position  
framework to accommodate the thickness of the finished wall (Figures 28 ).  
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the  
control compartment access panel. Any hearth extension used is for appearance only and does not  
have to conform to standard hearth extension installation requirements.  
Note: Combustible wall finish materials and/or surround materials must not be allowed to  
encroach the area defined by the appliance front face (black sheet metal). Never allow  
combustible materials to be positioned in front of or overlapping the appliance front face.  
See Figures 28.  
Combustible Wall  
This Area Must Remain Clear  
of Combustible Materials  
Framing  
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance  
frontfacewiththeseexceptions:theymustnotcoveranyportionof theglass or louvers; they mustnotcover  
any portion of the top radiant panel and the air gaps surrounding the top radiant panel.  
1" Min  
(25 mm)  
Combustible  
Wall Framing  
Spacer  
Vertical installation clearances to combustible mantels vary according to the depth of the mantel.  
(See Figure 27). Mantels constructed of non-combustible materials may be installed at any height  
above the appliance opening; however, do not allow anything to hang below the hood.  
Combustible  
Finished Wall  
Materials May  
Top of Appliance  
Touch Top of  
MANTEL CLEARANCES  
Inches (mm)  
Unit  
Radiant panel  
Top of Door Frame  
12 (305) MANTEL  
Hood must be installed as shown.  
Clean Face Models  
10 (254) MANTEL  
8 (203) MANTEL  
Figure 28  
6 (152) MANTEL  
14  
12  
(356)  
4 (102) MANTEL  
2 (51) MANTEL  
(305)  
10  
(254)  
TOP OF  
APPLIANCE  
8
6
(203)  
(152)  
4
(102)  
NOTE - Hood shown as positioned  
in louvered front model. The hood  
position in the flush faced front model  
is lower than shown.  
*Note - The side walls of mantels may protrude  
beyond the front face of the fireplace a maximum  
of 5 inches (127mm) at 0 inch clearance to the  
sides of the fireplace.  
Figure 27  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
15  
 
GAS CONVERSION KITS  
WARNING: THIS CONVERSION KIT SHALL BE  
INSTALLED BY A QUALIFIED SERVICE AGENCY IN  
ACCORDANCE WITH THE MANUFACTURER'S IN-  
STRUCTIONS AND ALL APPLICABLE CODES AND  
REQUIREMENTS OF THE AUTHORIZED AGENCY  
HAVING JURISDICTION. IF THE INFORMATION IN  
THESE INSTRUCTIONS IS NOT FOLLOWED EX-  
ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF  
CARBON MONOXIDE MAY RESULT CAUSING  
PROPERTYDAMAGE,PERSONALINJURYORLOSS  
OFLIFE. THEINSTALLATIONISNOTPROPERAND  
COMPLETE UNTIL THE OPERATION OF THE CON-  
VERTEDAPPLIANCEISCHECKEDASSPECIFIEDIN  
THEOWNERINSTRUCTIONSSUPPLIEDWITHTHE  
KIT.THEQUALIFIEDSERVICEAGENCYPERFORM-  
ING THIS INSTALLATION ASSUMES RESPONSI-  
BILITY FOR THIS CONVERSION.  
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION  
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SER-  
VICE CONFORMÉMENT AUX INSTRUCTIONS DU  
FABRICANT ET TOUTES EXIGENCES ET CODES  
APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION.  
SI L'INFORMATION DANS CETTE INSTRUCTION N'EST  
PASSUIVIEEXACTEMENT,UNFEU,EXPLOSIONOUPRO-  
DUCTIONDEPROTOXYDEDECARBONEPEUTRÉSULTER  
LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU  
BLESSUREPERSONNELLEDEVIE. L'AGENCEQUALIFIÉE  
DE SERVICE EST ESPONSABLE DE L'INSTALLATION  
PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST  
PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE  
L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES  
CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE  
PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.  
In Canada:  
b. Remove the bottom control compartment  
Natural To Propane Gas Conversion Kit  
THE CONVERSION SHALL BE CARRIED OUT  
IN ACCORDANCE WITH THE REQUIREMENTS  
OF THE PROVINCIAL AUTHORITIES HAVING  
JURISDICTION AND IN ACCORDANCE WITH  
THE REQUIREMENTS OF THE CAN1-B149.1  
AND .2 INSTALLATION CODE.  
access panel by compressing the spring-  
loaded hinge pin on the left side until it  
disengages from the left cabinet panel  
hole. Pull the panel away from the fire-  
place. See Figure 20 on page 12.  
Models No. Unit Type  
Catalog No.  
H2198  
millivolt  
EBVST  
EBVPF  
electronic  
H2200  
c. Remove the modesty panel by pulling the  
bottom right corner of the modesty panel  
out slightly to disengage the snap-fit fea-  
ture; lift the modesty panel by the tab on  
the panel's right end, pull the right end of  
the panel away from the cabinet and then  
pull the panel diagonally out of the left side  
cabinet panel slots. (In the above proce-  
dure, reverse the words "left" and "right"  
for EBVCR models). Remove the modesty  
panel carefully, so that none of the wires  
become loose or disconnected.  
d. Locate the latch at the top of the control  
compartment.Todisengagethelatchfrom  
the bottom vee-flange of the glass enclo-  
sure panel, reach for the handles located  
towards the back of the latch and pull the  
handl down toward the front of the unit.  
e. Swing the bottom of the door out and raise  
it slightly to lift the top flange of the door  
frame away from the appliance.  
Natural To Propane Gas Conversion Kit  
LA CONVERSION DEVRA ÊTRE EFFECTUÉE  
CONFORMÉMENTAUXRECOMMANDATIONS  
DES AUTORITÉS PROVINCIALES AYANT  
JURIDICTION ET CONFORMÉMENT AUX  
EXIGENCESDUCODED'INSTALLATIONCAN1-  
B149.1 ET.2.  
Models No. Unit Type  
Catalog No.  
H2198  
millivolt  
EBVCR  
EBVCL  
electronic  
H2200  
Propane to Natural Gas Conversion Kit  
Gas conversion kits are available to convert  
your appliance from the use of one type of gas  
to the use of another. These kits contain all the  
necessary components needed to complete  
the task including labeling that must be affixed  
to ensure safe operation.  
Model No.  
Unit Type  
millivolt  
Catalog No.  
H2199  
EBVST  
EBVPF  
electronic  
H2201  
Propane to Natural Gas Conversion Kit  
Kitpartnumbersarelistedhereandthefollow-  
ing steps detail the conversion procedure.  
Model No.  
Unit Type  
millivolt  
Catalog No.  
H2203  
Step 1. Turn off the gas supply to the appliance.  
a. Openthecontrolcompartmentaccesspanel,  
by actuating the spring-loaded magnetic  
catches securing the panel, gently depress-  
ingtheoutertopcornersofthepaneluntilthe  
catches"pop"thepanelfreeandallowingitto  
swing out and down to open.  
EBVCR  
EBVCL  
electronic  
H2205  
Step 2. Carefully remove the logs. Exercise  
care as not to break the logs.  
Step 3. Referring to Figure 29 on page 17,  
remove the burner.  
16  
 
PAN BURNER  
Inlet Pressure Test Port  
Pressure  
Regulator  
Manifold  
Pressure  
Test Port  
Remove  
These  
Components  
Slotted  
Cap  
FIREBOX BOTTOM  
BACK OF FIREPLACE  
Spring  
Figure 30  
Adjusting  
Screw  
Step 6. Refer to Figure 31 and remove the  
pilot hood assembly to access the hexed pilot  
orifice. Remove and replace the orifice with  
the one provided with the kit.  
BURNER POSITIONING  
Figure 32  
PAN  
BURNER  
See Figure 33 and replace the pilot orifice as  
follows: Remove the ignitor assembly retainer  
clip, andcarefullyremovetheignitorassembly.  
Exercise extreme care to prevent damage to  
or breakage of the ignitor assembly. Remove  
the screw securing the pilot assembly to its  
mounting bracket. Back off the flare nut at the  
end of the pilot gas line to free the pilot assem-  
bly from the gas line. Remove the pilot orifice  
and replace it with the one provided with the  
conversion kit. Reinstall the pilot assembly by  
reversing the steps detailed here.  
PILOT ASSEMBLY  
Pilot  
Orifice  
Figure 29  
When reinstalling the ignitor assembly, use  
extreme care to prevent damage and break-  
age. Do not apply any leverage to the ignitor  
assembly while restoring the retainer clip to  
its original position.  
Figure 31  
Millivolt Appliances  
Electronic Appliances  
Step 4. SIT Systems - Refer to Figure 30 and  
the instructions provided with the kit. Using a  
Torx T20, remove and discard the three pres-  
sure regulator mounting screws. Remove the  
pressure regulator, spring, poppet, diaphragm  
and bushing. Discard all removed compo-  
nents. Ensure the rubber gasket installed on  
the back of the replacement pressure regulator  
is properly positioned and install the new pres-  
sure regulator using the new screws supplied  
with the kit. Tighten screws to 25 In. lb. torque.  
Step 7. Honeywell Electronic Valves - See  
Figure 32 and the instructions provided with  
the kit. Remove the slotted cap screw, o-ring,  
pressure-regulating adjusting screw and  
spring. Retain all parts for possible later use.  
Install new components from the kit. Black  
cap and red spring for propane gas units.  
Silvercapandstainlesssteelspringfronatural  
gas units.  
Pilot  
Assembly  
Pilot  
Orifice  
Ignitor  
Assembly  
Before installing the cap, attach manometer  
to the manifold side pressure test fitting and  
adjust screw until pressure reads 3.5 inches  
water column (0.87 kPa) for natural gas, and  
10.0 inches water column (2.49 kPa) for  
propane gas.  
Step5.Attachmanometertothemanifoldside  
pressure test fitting and verify manifold pres-  
sure reads 3.5 inches water column (0.87 kPa)  
for natural gas, and 10.0 inches water column  
(2.49 kPa) for propane gas.  
Retaining  
Clip  
Flare Nut  
Note: If the ignitor is damaged, a replace-  
ment kit is available, order Catalog Number  
87L54.  
Figure 33  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
17  
 
All Models  
Step 9. Reassemble the remaining compo-  
nents by reversing the procedures outlined in  
the preceding steps. Use pipe joint compound  
or Teflon tape on all pipe fittings before install-  
ing (ensure propane resistant compounds are  
used in propane applications, do not use pipe  
joint compounds on flare fittings).  
Kit Catalog No.  
H2199 and H2201  
Step 8. (Refer to Figure 29 )  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
NATURAL GAS  
A. Remove the orifice from the manifold  
andreplaceitwiththeoneprovidedinthe  
kit. See the following table for orifice  
sizes for natural and propane models.  
Figure 34 illustrates the orifice.  
INPUT BTU/HR  
MANIFOLD PRESSURE  
ORIFICE SIZE #32  
37,500  
3.5"  
Step 10. Attach the conversion label provided  
in the conversion kit to the rating plate on the  
appliance. Figure 35 shows all of the labels for  
all of the kits covered by this manual as shown  
in the tables on page 17. Compare the label  
provided in the kit being installed to the appro-  
priate label shown in Figure 35.  
Kit Catalog No.  
H2203 and H2205  
B. InstalltheburnersasshowninFigure29.  
The primary air opening can be adjusted  
by removing the venturi tube air shutter  
securing screw and placing it in the other  
hole provided nearby. The correct hole  
usage for this screw for the gas being  
used can be determined by the air shutter  
gap indicated in Figure 25 on page 14.  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
NATURAL GAS  
INPUT BTU/HR  
MANIFOLD PRESSURE  
ORIFICE SIZE #34  
34,000  
3.5"  
Step 11. Turn on the gas supply and test for  
leaks as shown in step 5 on page 11.  
Kit Catalog No.  
H2198 and H2200  
Elevation  
Feet  
(meters)  
Orifice size  
Model  
No.  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
Nat. Prop.  
PROPANE/LPG  
EBVST  
EBVPF  
INPUT BTU/HR  
MANIFOLD PRESSURE  
ORIFICE SIZE #50  
34,000  
#32  
#34  
#50  
#50  
10.0"  
0-4500  
(0-1372)  
EBVCR  
EBVCL  
Figure 35  
Figure 34  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
18  
 
NOTES:  
19  
 
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,  
materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2004 by LENNOX HEARTH PRODUCTS  
P/N 850,025M REV. B 01/2007  
1110 West Taft Avenue Orange, CA 92865  
 

MTD Blower 60 3857 0 User Manual
National Instruments Graphics Tablet NI 4070 4072 6 1 2 Digit FlexDMM User Manual
NEC Laptop Versa M540 User Manual
Nextar GPS Receiver X30908EH02 User Manual
Nilfisk ALTO Vacuum Cleaner SR 1900 D User Manual
Oki Fax Machine 5950 User Manual
Omron Computer Hardware CJ1H User Manual
Palsonic CRT Television 6830GY User Manual
Panasonic DVD Player DVD F61 User Manual
Panasonic Flat Panel Television 58PF12UK User Manual