INSTALLATION
INSTRUCTIONS
B-VENT MULTI-OPEN
ELITE® SERIES
This appliance may be installed in an aftermarket perma-
nently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance
is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
B-VENTED GAS FIREPLACES
P/N 850,025M REV. B 01/2007
MODELS
Millivolt Models
EBVSTNM EBVSTPM
EBVPFNM EBVPFPM
EBVCRNM EBVCRPM
EBVCLNM EBVCLPM
Electronic Models
EBVSTNE EBVCRNE
EBVPFNE EBVCLNE
In the Commonwealth of Massachusetts & New York:
• Installation must be performed by a licensed plumber or
gas fitter.
See Table of Contents for location of additional New York
& Commonwealth of Massachusetts requirements.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:IFTHEINFORMATIONINTHISMANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-
SION MAY RESULT CAUSING PROPERTY DAM-
AGE, PERSONAL INJURY OR LOSS OF LIFE.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LESINSTRUCTIONSDONNÉDANSCETTENOTICEPOUR
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE
BLESSURE OU LA MORT.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicin-
ity of this or any other appliance.
POURVOTRESÉCURITÉ: Nepasentreposerniutiliser
d'essencenid'autrevapeursouliquidesinflammables
dans le voisinage de cet appareil ou de tout autre
appareil.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Netouchezàaucuninterrupteur. Nepasvousservir
des téléphones se trouvant dans le batiment où
vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
• Ifyourgassuppliercannotbereached, callthe
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
L'installationetservicedoitêtreexécutéparunqualifié
OTL Report No. 116-F-07A-5
installeur,agencedeserviceoulefournisseurdegaz.
S'assurerquelebrùleuretlecompartimentdes
commandes sont propres. Voir les instruc-
tions d'installation et d'utilisation qui
accompagnent l'appareil.
Table 1 shows the units' gas orifice size
for the elevations indicated.
Maximum inlet gas supply pressure to these
appliances is 10.5 inches water column (2.61
kPa) for natural gas and 13.0 inches water
column (3.23 kPa) for propane.
Orifice size
Model
No.
Elevation
Feet (meters)
These appliances must be isolated from the gas
supplypipingsystem(byclosingtheirindividual
manualshut-offvalve)duringanypressuretest-
ing of the gas supply piping system at test
pressures equal to or less than¹⁄₂ psig (3.5 kPa).
Provide adequate clearances around air open-
ings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front, back and/or side viewing surfaces of
the appliance.
Nat. Prop.
EBVST
EBVPF
#32
#34
#50
#50
0-4500
(0-1372)
EBVCR
EBVCL
These appliances and their individual shut-off
valves must be disconnected from the gas supply
piping system during any pressure testing of that
systematpressuresinexcessof¹⁄₂psig(3.5kPa).
These appliances are designed to operate on
naturalorpropanegasonly.Theuseofotherfuels
or combination of fuels will degrade the perfor-
mance of this system and may be dangerous.
Table 1
Themillivoltappliancesaremanuallycontrolled
and feature a spark ignitor (piezo) that allows
theappliance'spilotgastobelitwithouttheuse
of matches or batteries. This system will still
function in the event of a power outage.
These appliances must not be connected to
a chimney or flue serving a separate solid
fuel burning appliance.
Millivolt Models -
Millivolt models come standard with the
manually-modulated gas valve; flame ap-
pearance and heat output can be con-
trolled at the gas valve. Input of millivolt
models is shown in the following table:
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or
nausea. If you have these signs, obtain
fresh air immediately. Turn off the gas
supply to the appliance and have it ser-
viced by a qualified professional, as it may
not be operating correctly.
Do not use these appliances if any part has
been under water. Immediately call a quali-
fied, professional service technician to inspect
the appliance and to replace any parts of the
control system and any gas control which
have been under water.
Millivolt Models
Natural and Propane
Gas Models
EBVSTNM, EBVPFNM,
EBVSTPM, EBVPFPM,
EBVCLNM, EBVCRNM,
EBVCLPM, EBVCRPM
Input rate (BTU/H)
Manually-modulated
30,000 TO 37,500
27,000 TO 34,000
28,000 TO 34,000
27,000 TO 34,000
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
untechnicienqualifiépourinspecterl'appareilet
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'eau.
WARNING: B-VENTAPPLIANCESARENOT
DESIGNED TO OPERATE IN NEGATIVELY
PRESSUREDENVIRONMENTS(PRESSURE
WITHIN THE HOME IS LESS THAN PRES-
SURES OUTSIDE). SIGNIFICANT NEGA-
TIVELY PRESSURED ENVIRONMENTS
CAUSED BY WEATHER, HOME DESIGN,
OR OTHER DEVICES MAY IMPACT THE
OPERATION OF THESE APPLIANCES.
NEGATIVE PRESSURES MAY RESULT IN
POOR FLAME APPEARANCE, SOOTING,
DAMAGE TO PROPERTY AND/OR SEVERE
PERSONAL INJURY. DO NOT OPERATE
THESEAPPLIANCESINNEGATIVELYPRES-
SUREDENVIRONMENTS. PROVIDINGAD-
EQUATE VENTILATION TO THE APPIANCE
FORCOMBUSTIONAIRWILLELIMINATEA
NEGATIVE PRESSURE ENVIRONMENT.
Electronic Models -
Electronic models have a fixed rate gas valve.
Input of electronic models is shown in the
following table:
This appliance may be installed in an af-
termarket permanently located, manufac-
tured home (USA only) or mobile home,
where not prohibited by local codes. This
appliance is only for use with the type of
gas indicated on the rating plate. This ap-
pliance is not convertible for use with
other gases, unless a certified kit is used.
Electronic Models*
Input rate (BTU/H)
Natural Gas Models
Fixed Rate
EBVSTNE, EBVPFNE,
EBVCLNE, EBVCRNE,
37,500
34,000
* See page 16 for Electronic Models conversion from
Natural gas to Propane.
Cetappareilpeutêtreinstallédansunmaison
préfabriquée (É.-U. seulement) ou mobile
déjà installée à demeure si les réglements
locaux le permettent.
All Models -
Maximum manifold pressure is 3.5 in. w.c.
(0.87 kPa) for natural gas and 10 in. w.c.
(2.49 kPa) for LP/Propane gas.
Cet appareil doit être utilisé uniquement avec
les types de gaz indiqués sur la plaque
signalétique. Nepasl'utiliseravecd'autresgaz
sauf si un kit de conversion certifié est installé.
Installations at Altitudes of 0 to 4500 ft.-
Units are tested and approved for elevations
of 0 to 4500 feet (0 to 1372 meters).
WARNING: FAILURE TO COMPLY WITH
THEINSTALLATIONANDOPERATINGIN-
STRUCTIONS PROVIDED IN THIS DOCU-
MENT WILL RESULT IN AN IMPROP-
ERLY INSTALLED AND OPERATING AP-
PLIANCE,VOIDINGITSWARRANTY. ANY
CHANGE TO THIS APPLIANCE AND/OR
ITS OPERATING CONTROLS IS DANGER-
OUS. IMPROPERINSTALLATIONORUSE
OF THIS APPLIANCE CAN CAUSE SERI-
OUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON MON-
OXIDE POISONING.
Test gage connections are provided on the
front of the millivolt gas control valve (iden-
tified IN for the inlet and OUT for the mani-
fold side). A ¹⁄₈" NPT test gage connection is
provided at the inlet and outlet side of
the electronic gas control valve.
Installations at Altitudes above 4500 ft.-
For elevations above 4500 feet (1372
meters), install the unit according to the
regulations of the local authorities having
jurisdictionand,intheUSA,thelatestedition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the
CAN1-B149.1 and .2 codes.
Minimum inlet gas pressure to these appliances
is5.0 incheswatercolumn(1.24kPa)fornatural
gasand11.0incheswatercolumn(2.74kPa)for
propane for the purpose of input adjustment.
3
Gas vent caps that are located 8' or more from
a portion of a building which extends at an
angle greater than 45° upward from the hori-
zontal may terminate in accordance with (Fig-
ure 3 ), provided that in no case shall any
discharge opening on the cap be less than 2'
(610 mm) horizontally from the roof surface
(National Fuel Gas Code ANSI Z223.1 (NFPA
54) 7.6.2) (CAN/CGA B149).
TYPICAL LOCATIONS
*When See-Through (EBST-2) is
installed with one side flush
with a wall,opposite wall must
n o t e x t e n d b e y o n d e i t h e r
viewing side of the fireplace.
Corner - Left
(EBCL-2)
Corner - Right
(EBCR-2)
**See-Through
(EBST-2)
Bay
(EBBAY)
These instructions should be used as a
guideline and do not supersede local codes
in any way.
Peninsula
(EBPF-2)
**When See-Through (EBST-2) is
installed in the middle of a room,
do not extend side walls beyond
either viewing side of the fireplace.
*See-Through
(EBST-2) -
one side flush with a wall
Multiple Terminations – These appliances
may vent adjacent to and at the same level
with any other gas appliances (including di-
rect-vent appliances) provided that there is at
least 2 ft. (0.6m) between the proximal edges
of the vent caps. These appliances may be
vented adjacent to a chimney vent servicing a
solid fuel fireplace provided the B-vent cap is
at least 2 ft. (0.6m) away from the nearest
point of the chimney opening.
Figure 2
APPLIANCE AND VENT CLEARANCES
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OFHIGHSURFACETEMPERATURES.USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CARE-
FULLY SUPERVISED WHEN THEY ARE IN
THE SAME ROOM AS THE APPLIANCE.
The appliance is approved with zero clear-
ance to combustible materials on all sides (as
detailed in Table 2), with the following excep-
tion: When the unit is installed with one side
flush with a wall, the wall on the other side of
the unit must not extend beyond the front
edge of the unit.
Note: Venting terminals shall not be recessed
into a wall or siding.
WARNING: DO NOT PLACE CLOTHING
OR OTHER FLAMMABLE MATERIALS
ON OR NEAR THIS APPLIANCE.
1/2 in. (13 mm)
BACK
0 in. (0 mm) spacers
1/2 in. (13 mm)
SIDES
X
12
Roof Pitch is X/12
0 in. (0 mm) spacers
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDESÀ VAPEURINFLAMMABLES À
COTE DE L'APPAREIL.
TOP SPACERS
FLOOR
0 in. (0 mm)
0 in. (0 mm)
From Bottom
of Unit to
Ceiling
Minimum Height from Roof
to Lowest Discharge Opening
64 in. (1626 mm)
These appliances are equipped with an inte-
gral combustion air door and actuator arm.
Combustion air kits are optional.Install as
shown in Step 6 on page 12.
VENT
1 in. (25.4 mm)
Minimum Height
from Roof to Lowest
Discharge Opening
SERVICE CLEARANCES
Roof Slope
VIEWING
SIDES -
(FRONT, BACK
OR SIDE)
LOCATION
In selecting the location, the aesthetic and func-
tional use of the appliance are primary concerns.
However, vent system routing to the outside
atmosphere and access to the fuel supply are
alsoimportant. Considerationshouldbegivento
trafficways,furniture,draperies,etc.,duetohigh
surface temperatures (Figure 2 ). The location
should also be free of electrical, plumbing or
other heating/air conditioning ducting.
3 Feet. (0.9 meters)
Feet
1' 0"
2' 0"
4' 0"
6' 0"
8' 0"
Meters
0.3
Flat to 6/12
Over 7/12 to 9/12
Over 10/12 to 12/12
Over 13/12 to 16/12
Over 17/12 to 21/12
0.6
Table 2
1.2
1.8
In addition, when the unit is installed in the
middle of a room, the side walls surrounding
the unit must not extend beyond the front or
rear edge of the unit. See Figure 2.
2.4
Figure 3
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materi-
als. However, if installed on combustible mate-
rials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.
Vertical Vent Termination Clearances
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows,
however,eachinstallationisuniqueresultingin
variations to those described.
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or
similar obstruction.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
4
See the page numbers references in the follow-
ing steps for detailed procedures.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed. Headers may be in direct contact
with the appliance top spacers but must not be
supported by them or notched to fit around
them. All construction above the appliance
must be self supporting, DO NOT use the
appliance for structural support.
Top Radiant
Panel
Step 1. (page 5) Construct the appliance
framing. Position the appliance within the
framing and secure with nailing brackets.
Step 2. (page 5) Route gas supply line to
appliance location.
Top Bustle
Bottom
Bustle
Control
Compartment
Access Panel
Step 3. (page 5) Install the vent system
and exterior termination.
Step 4. (page 10) Field Wiring
a. Millivolt Appliances – The operating con-
trol switch is factory installed.
b. Electronic Appliances – Connect 120 Vac
electrical power to the appliance receptacle.
Step 5. (page 11) Make connection to gas
supply.
Step 6. (page 12) OutsideAirKitInstallation
Step 7. (page 13) Install the log set, ver-
miculite and glowing embers.
Step 8. (page 13) Checkout appliance op-
eration.
Step 9. (page 13) Install glass enclosure
panels.
Step 10. (page 14) Burner Adjustment.
Step 11. (page 14) Spillage Test and Safety
Limit Switch Operation.
Unit Parts Identification
Side Nailing Flanges
Figure 4
Thefireplaceshouldbesecuredtotheframingat
the side(s) and/or rear of the unit using the
factory-provided nailing flanges. Install the nail-
ing flanges - 8 (EBVST), 4 (EBVPF, EBVCL,
EBVCR)-asshowninFigure5usingtheexisting
screws. Position the fireplace within the fram-
ing. When required, the flanges may be bent 90
degrees by hand or with the assistance of a
hammer. Use woodscrewstosecurethenailing
flangestotheframing.SeeTable2onpage4for
clearances of framing members to cabinet parts
in the nailing flange area. The nailing flange itself
is exempt from these clearances.
3- Open the control compartment access
panel, by actuating the spring-loaded mag-
netic catches securing the panel, gently de-
pressing the outer top corners of the panel
until the catches "pop" the panel free and
allowingittoswingoutanddowntoopen. See
Figure 20 on page 12.
4 - Open the latches (located on the left and
right sides of the unit front opening, under the
fireboxfloor)securingtheglassenclosurepanel.
Remove the panel by tilting it outward at the
bottom and lifting it up. Set the door aside
protecting it from inadvertent damage. See
Figure 24 on page 13.
Floor Nailing Tabs
Secure the fireplace to the floor as shown in
Figure 5.
Step 12. (page 15) Install the hoods.
Step 1. FRAMING
Step 2. ROUTING GAS LINE
DETAILED INSTALLATION STEPS
Route a ¹⁄₂" (13 mm) gas line as shown in
Figures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or
11 (EBVCR) on pages 6 and 7. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations.
Frame these appliances as illustrated in Fig-
ures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or
11 (EBVCR) on pages 6 and 7. All framing
details must allow for a minimum clearance
to combustible framing members as shown
inTable 2 on page 4.
The appliance is shipped with all gas controls
and components installed and pre-wired.
1 - Remove the shipping carton.
2 - Removethetopradiantpanel;seeFigure4.
All appliances are factory-equipped with a flex-
iblegaslineconnectorand¹⁄₂inchshutoffvalve.
(See step 5 on page 11).
EBVST SHOWN
EBVCL SHOWN
(FOR EBVCR VIEW, INTERCHANGE SIDES)
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)
Remove these two screws and use them
when installing the nailing flanges.
Step 3. Install the Vent System &
Exterior Termination -
In the United States, vent installation must
conform with local building codes. In the ab-
senceoflocalcodes,ventsmustbeinstalledin
accordance with the current edition of the
National Fuel Gas Code (ANSI-Z223.1).
In Canada, vent installation must conform
with local building codes. In the absence of
local codes, vents must be installed in ac-
cordance with the current edition of the Na-
tional Standard of Canada CAN/CGA-B149.1
or B149.2 Installation Code.
Nailing
Flanges
Turn tabs down and secure to the floor with
8d nails or other appropriate fasteners on all sides
of the unit which do not have viewing glass panels.
This gas fireplace must be vertically vented
using listed 6 in. type-B, double-walled vent
pipe and a listed vent termination.
Figure 5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Slip the first 6 inch (152 mm) section of B-
Vent over the fireplace flue outlet and secure
with four sheetmetal screws (# 8 or larger),
and install the remainder of the B-Vent to the
outside. Minimum overall height of the vent
system and appliance must be 10' (2.54 m)
vertical - no offset (see Figure 6 ); or 12' (3.7
m) when an offset up to 60 degrees from the
vertical is used - this offset may start at the
fireplace flue collar (see Figure 7 ). The
maximum overall height of the vent system
and appliance should not exceed 40 feet.
60 degrees
max.
10 ft.
12 ft.
Minimum
Minimum
Install the B-vent system in accordance with
the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE
VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers in-
stallation instructions for variations of vent-
ing techniques. If common venting of sev-
eral units is contemplated, it should be dis-
cussed with an architect and the local Build-
ing Department.
Figure 6
Figure 7
Do not place insulation materials within 1 in.
of the gas vent system.
FIREPLACE FRAMING SPECIFICATIONS
EBVST
(See-Through)
EBVPF
(Peninsula)
Minimum Framing
Stud size is 2 x 4
Minimum Framing
Stud size is 2 x 4
inches (millimeters)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
6¹⁄₄
(159)
6¹⁄₄
(159)
*41¹⁄₂
(1054)
*41¹⁄₂
(1054)
22³⁄₄**
(578)
22³⁄₄**
(578)
40¹⁄₈
(1019)
41¹⁄₂
(1054)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Figure 8
Figure 9
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
6
FIREPLACE FRAMING SPECIFICATIONS CONTINUED
EBVCL (Corner-Left)
Minimum Framing
Stud size is 2 x 4
EBVCR (Corner-Right)
Minimum Framing
Stud size is 2 x 4
inches (millimeters)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
*41¹⁄₂
(1054)
Gas Line
*41¹⁄₂
(1054)
Center of gas line
is 3 in. (76 mm)
up from floor.
9³⁄₄
(248)
6¹⁄₄
(159)
40¹⁄₈
(1019)
40¹⁄₈
(1019)
9⁷⁄₈
(251)
Optional Gas Line
Location Center of gas line
is 3 in. (76 mm) up from floor.
24
(610)
24
(610)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier
fireplace installation, if unit is installed after framing is erected.)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension
permits easier fireplace installation, if unit is installed after framing is erected.)
Figure 11
Figure 10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
FIREPLACE SPECIFICATIONS
20¹⁄₁₆
(510)
FINISH WALL BRACKET
(Front and back edge of unit top)
EBVST (See-Through)
Figure 12
12 (305)
B
A
1/2
(13)
FRAMING SPACERS
(Top and Both Sides)
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
DETAIL OF
FINISH WALL BRACKET
40¹⁄₈
(1019)
TOP VIEW
2³⁄₄
(70)
¹⁄₂ (13)
¹⁄₂ (13)
24
(610)
40¹⁄₈
(1019)
12
(305)
4 (102)
OUTSIDE AIR
SHUTTER
41
(1041)
ELECTRICAL
INLETS
37
(940)
ELECTRICAL
INLETS
GAS INLET
3 (76)
GAS INLET
4⁹⁄₁₆
(116)
4⁹⁄₁₆
(116)
3 (76)
6⁷⁄₈
(175)
6⁷⁄₈
CONTROL
COMPARTMENT
ACCESS PANEL
(175)
FRONT VIEW
LEFT SIDE VIEW
RIGHT SIDE VIEW
20¹⁄₁₆
(510)
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
FRAMING SPACERS
(Top and Side)
EBVPF (Peninsula)
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
12 (305)
Figure 13
B
A
DETAIL OF
FINISH WALL BRACKET
¹⁄₂
(13)
¹⁄₂
(13)
40¹⁄₈
(1019)
TOP VIEW
2³⁄₄
(70)
24
(610)
12
(305)
4 (102)
OUTSIDE AIR
SHUTTER
41
37
(1041)
(940)
ELECTRICAL
INLETS
GAS INLET
4⁹⁄₁₆
(116)
3 (76)
CONTROL COMPARTMENT
ACCESS PANEL
6⁷⁄₈
(175)
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
8
FIREPLACE SPECIFICATIONS CONTINUED
20¹⁄₁₆
(510)
EBVCL (Corner-Left)
Figure 14
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
12 (305)
B
A
DETAIL OF
FINISH WALL BRACKET
FINISH WALL BRACKET
(Front and left edge of unit top)
¹⁄₂
(13)
FRAMING SPACERS
(Top, Side and Back)
40¹⁄₈
(1019)
¹⁄₂
(13)
TOP VIEW
2³⁄₄
(70)
¹⁄₂
(13)
12
(305)
24
(610)
4 (102)
OUTSIDE AIR
SHUTTER
37
(940)
41
(1041)
ELECTRICAL
INLETS
GAS INLET
4⁹⁄₁₆
(116)
3 (76)
CONTROL COMPARTMENT
ACCESS PANEL
6⁷⁄₈
(175)
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
20¹⁄₁₆
(510)
TOP VIEW
EBVCR (Corner-Right)
Figure 15
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
12 (305)
B
A
DETAIL OF
FINISH WALL BRACKET
FRAMING SPACERS
(Top, Side and Back)
FINISH WALL BRACKET
(Front and right edge of unit top)
¹⁄₂
(13)
40¹⁄₈
(1019)
2³⁄₄
(70)
¹⁄₂
24
(610)
12
(305)
(13)
4 (102)
41
(1041)
OUTSIDE AIR
SHUTTER
37
(940)
ELECTRICAL
INLETS
GAS INLET
3 (76)
6⁷⁄₈
(175)
CONTROL COMPARTMENT
ACCESS PANEL
RIGHT SIDE VIEW
FRONT VIEW
LEFT SIDE VIEW
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
3. Remove the bottom control compartment
access panel by compressing the spring-
loaded hinge pin on the left side until it
disengages from the left cabinet panel
hole. Pull the panel away from the fire-
place. See Figure 20 on page 12.
Step 4. FIELD WIRING
Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced,
it must be replaced with Type AWM 105°C – 18 GA. wire.
Refer to Section A for millivolt appliances and
Section B for electronic appliances. The gas
valve is set in place and pre-wired at the
factory on both models.
White
4. Remove the modesty panel by pulling the
bottom edge of the modesty panel out of
the locking slots of the cabinet bottom.
Then tilt the top edge at a 45° angel and
lift out. Remove the modesty panel care-
fully, so that none of the wires become
loose or disconnected.
5. Remove the outlet receptacle by remov-
ing the two securing screws. See Figure
17. (The left and right designations used
here are reversed in EBVCR applications.)
6. Install a field-provided strain relief in the
cabinet knockout opening for the protec-
tion of the power supply wires.
A. Millivolt Wiring (See Figure 16 )
Thermopile
1. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed in
the modesty panel. Optional wall-mounted
switch, thermostat, or one of the optional
remote control kits may also be used.
2. If wall-mounted ON/OFF control or thermo-
stat is selected, mount it in a convenient
location on a wall near the fireplace.
Black
Field Wired
Factory Wired
APPLIANCE-MOUNTED ON/OFF SWITCH
*OPTIONAL WALL-MOUNTED ON/OFF
SWITCH OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
*Turn the appliance-mounted ON/OFF burner control
switch to the OFF position if an optional
control switch is installed.
3. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 con-
ductor wire supplied with the unit.
Schematic Representation Only
7. Connect the power supply wires to the
receptacle as shown in Figure 18 on
page 11.
Figure 16
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor con-
nected to the gas valve circuit and the other
end of each conductor placed loose inside
the lower compartment of the unit.
B. Electronic Wiring
(also see Figure 18 on page 11 )
8. Connect the ground supply wire and the
green wire attached to the outlet
receptacle's green ground screw.
9. Appliance-mounted ON/OFF burner con-
trol switch (rocker switch) is factory in-
stalled in the modesty panel. Optional
wall-mounted switch, thermostat, or one
of the optional remote control kits may
also be used.
Note: The electronic appliance must be con-
nected to the main power supply.
Caution: do not connect the optional wall
switch to a 120V power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Open the control compartment access
panel, by actuating the spring-loaded
magnetic catches securing the panel,
gently depressing the outer top corners
of the panel until the catches "pop" the
panel free and allowing it to swing out
and down to open.
4. If an optional control switch is installed,
turntheappliance-mountedON/OFFburner
control switch to the OFF position.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
10
10. Ifwall-mountedON/OFFswitchorthermo-
stat is to be used, mount it in a convenient
location on a wall near the fireplace.
11. If the wall-mounted ON/OFF switch is to be
used, wire it to the the low voltage circuit
as shown in Figure 18.
Electronic Wiring Diagram (Honeywell)
FIREBOX BOTTOM
JUNCTION BOX
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA.
wire.
OUTLET RECEPTACLE
CABINET
RIGHT SIDE
PANEL
2. 120V, 60Hz – Less than 3 amps.
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
*ON/OFF Switch (Integral
with Gas Valve)
Gas Valve
PILOT
ASSEMBLY
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
the gas valve circuit and the other end of each
conductor placed loose inside the lower com-
partment of the unit.
BK
R
Green
BL
White
Black
Ground - Green
Neutral - White
120 VAC - Black
Junction Box
Tab Intact
Ta b
Broken
12. After wiring is complete, reinstall the out-
let receptacle; install the field-provided
the metal junction box cover plate; rein-
stall the modesty panel.
Red
Optional
Accessory
Switch
Green
Ground
Screw
Hot
Neutral
Side of
Receptacle
Side of
Receptacle
W
Transf.
120 V.
B
G
OUTLET RECEPTACLE
BOX SECURING SCREW
Note:ThegasvalveON/OFFswitchisshownin
Figure 18. It is integral with the gas valve and
should be set to the ON position.
24 V
BL
EBST-2, EBPF-2
R
AND EBCL-2 OUTLET RECEPTACLE SHOWN.
EBCR-2 HAS THE OUTLET RECEPTACLE LOCATED IN
THE LEFT CORNER OF THE UNIT
WT
BK
WT
EBBAY OUTLET RECEPTACLE LOCATED IN
THE REAR LEFT CORNER OF THE UNIT
IMPORTANT: Ground supply wire must
be connected to the green wire attached
to the outlet receptacle's green ground
screw. See Figure 18. Failure to do so
will result in a potential safety hazard.
The appliance must be electrically
grounded in accordance with local codes
or, in the absence of local codes, the
National Electrical Code, ANSI/NFPA 70-
(latest edition). (In Canada, the current
CSA C22-1 Canadian Electrical Code.)
LIMIT SWITCH
**OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE
RECEIVER
VIEW OF RIGHT BOTTOM CORNER OF UNIT
APPLIANCE-MOUNTED ON/OFF SWITCH
**Turn the appliance-mounted ON/OFF burner control switch to
the OFF position if an optional control switch is installed.
OUTLET RECEPTACLE INSTALLATION
Figure 17
Factory Wired
Field Wired
Schematic Representation Only
Figure 18
Step 5. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line.
Figure 19 on page 12 illustrates two methods
for connecting the gas supply. The flex-line
method is acceptable in the U.S., however,
Canadian requirements vary depending on lo-
cality. Installation must be in compliance with
local codes.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Step6. OutsideAirKits–Optional outsidemake-
up air kits, Model FOAK-4 or FAOK-4LD, may be
used with these appliances. Refer to the installa-
tion instructions packaged with the air kits for
specific installation information. If used, the out-
side air kit must be installed before the fireplace is
framed and enclosed in the finished wall.
Gas Flex Line Connector
Gas
Valve
³ꢀ₈" NPT ₂ ³ꢀ₈
Flare Fitting
¹ꢀ₂" x³ꢀ₈" Flare
Shut-Off Valve
³ꢀ₈ Flex Tubing
Outside air drawn into the fireplace supplies
air to the fire for combustion. Only one outside
air duct is necessary, if installed. See the
Figures on pages 8, 9 and 10 for the location
of the units outside air inlet.
Gas Stub
³ꢀ₈" Nipple
³ꢀ₈"Union
³ꢀ₈" Close Nipple
³ꢀ₈" Shut-Off Valve
If additional length of duct is necessary, pur-
chase locally available U.L. Class 0 or Class 1
metallic ducting. The duct may extend up to 50'
(15.24 m) in any direction.
¹ꢀ₂
x
³ꢀ₈"
Reducer
Figure 19 - GAS CONNECTION
These appliances are equipped with a gas flex
lineforuse(wherepermitted)inconnectingthe
unit to the gas line. A gas flex line is provided to
aid in attaching the B-vent appliance to the gas
supply.Thegasflexlinecanonlybeusedwhere
local codes permit. See Figure 19 for flex line
description. The flex line is rated for both natu-
ral and propane gas. A manual shut off valve is
also provided with the flex line.
Note: When installing the air duct vertically,
DO NOT terminate the duct closer than 3'
below the chimney top.
Outside combustion air ducting may be run
upwards or vertically through framing and
ceiling joists, with the hood installed through
an outside wall and 3' (1 m) below the termi-
nation. Ducting may also be run downward
through floor Joists and under the home to a
ventilated crawlspace not considered part of
the living area of the home.
The gas control valve is located in the lower
control compartment. To access the valve
proceed as follows:
Gas Valve
Hinge
Pin
Control
Compartment
Access panel
ON/OFF
Switch
Note: Do not terminate outside air kit in attic
space under any circumstances.
1- Openthecontrolcompartmentaccesspanel,
(Figure 20 ) by actuating the spring-loaded
magnetic catches securing the panel, gently
depressingtheoutertopcornersofthepanel
until the catches "pop" the panel free and
allowing it to swing out and down to open.
2- Remove the bottom control compartment
access panel by compressing the spring-
loaded hinge pin on the left side until it
disengagesfromtheleftcabinetpanel hole.
Pull the panel away from the fireplace. See
Figure 20.
Piezo
Ignitor
Modesty Panel
Lock Slot
Modesty
Panel
CAUTION: NEVER LOCATE INLET WHERE IT
CAN BE BLOCKED BY SHRUBS, SNOW
DRIFTS, ETC. NEVER LOCATE INLET IN GA-
RAGE OR ANY AREA WHERE THERE IS AN-
OTHERFUELBURNINGAPPLIANCEORPROD-
UCTSEMITTINGCOMBUSTIBLEGASESSUCH
AS PAINT, GASOLINE, ETC. IN COLD CLI-
MATES, IT IS RECOMMENDED THE COMBUS-
TION AIR DUCT BE INSULATED.
Figure 20
Turn on gas supply and test for gas leaks using
a soapy water solution. Never use an open
flame to check for leaks.
A. Mix a 50% dish soap, 50% water solution.
3- Remove the modesty panel by pulling the
bottom edge of the modesty panel out of
the locking slots of the cabinet bottom.
Then tilt the top edge at a 45° angel and
lift out. Remove the modesty panel care-
fully, so that none of the wires become
loose or disconnected.
After completing the installation of the op-
tional outside air vent system, the outside air
control lever must be put in service and tested
to ensure proper operation before completing
any enclosure around the firebox. Failure to
do so may result in extensive and costly re-
work. Before the operation of the vent system
can be tested, the lever securing screw must
be removed. See Figure 21 on page 13.
B. Light the appliance (refer to the lighting
instructionsprovidedintheHomeowner'sCare
and Operation Instructions).
C. Brush all joints and connections with the
soapy water solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” posi-
tion. Either tighten or refasten the leaking
connection and retest as described above.
The millivolt control valve has a ³⁄₈"
(10 mm) NPT thread inlet port. The electronic
control valve has a ¹⁄₂" (13 mm) NPT thread inlet
port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x
10 mm) NPT fitting.
The hand operated outside air control lever is
located on the right side (EBVST, EBVPF, and
EBVCL) or left side (EBVCR) of the fireplace
opening. See Figure 21 on page 13.
D. When the gas lines are tested and leak free,
observe the individual tongues of flame on the
burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure pro-
pane resistant compounds are used in pro-
pane applications).
To open the outside air shutter, open the bottom
controlaccesspanel,reachintothegapbetween
the firebox bottom and the modesty panel, and
pull the outside air control lever all the way out.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
12
Theoutsideairshuttershouldbefullyopenwhen
the fireplace is in use and completely closed
when the fireplace is not being used. Closing it
whennotinusewillpreventoutsidecoldairfrom
entering the dwelling.
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lightings
of the appliance will not require such purg-
ing. Inspect the pilot flame (remove logs, if
necessary, handling carefully).
Step 9. INSTALLING GLASS ENCLOSURE
PANELS
1. Visually inspect the gasket on the backside
of the panels. The gasket surface must be
clean, free of irregularities and seated firmly.
2. Position the glass enclosure panel in front
of the firebox opening at a 45 degree angle and
engage the top flange over the lip at the top of
the firebox opening. See Figure 24.
Outside Air Control Lever with Stop Behind
Securing Screw
Millivolt Appliance Checkout
3. Swing the glass enclosure panel down and
back. Ensure the gasket seats evenly as the
panel draws shut. Engage the Vee-flanges at
the bottom of the panel with the latches; then
close the latches to secure the panel.
4. After installing the front glass enclosure
panel, reinstall the bottom control compart-
ment access panel by inserting the right side
locating pin into the right side cabinet panel
and then the left side spring-loaded pin into
the left side cabinet panel.
The pilot flame should be steady and, not lifting
or floating. Flame should be blue in color with
traces of orange at the outer edge.
The top ³⁄₈" (10 mm) at the pilot generator
(thermopile) and the top ¹⁄₈" min (tip) of the
quick drop out thermocouple should be en-
gulfed in the pilot flame. The flame should
project 1" (25 mm) beyond the hood at all three
ports (Figure 22).
Outside Air Shutter in the
Closed Position
Replace logs after pilot inspection.
Control Compartment Access Panel
Outside Air Control Lever
and Securing Screw Location
Lower Compartment Door and Hinge
To light the burner; turn “ON” the modesty
panel mounted ON/OFF switch and rotate the
gas valve control knob counterclockwise to
the “ON” position.
Top Flange
(Glass Enclosure
Panel Frame)
Modesty Panel
(EBVST, EBVPF and EBVCR Units Shown)
Figure 21
Front Glass
Enclosure Panel
Operate the actuator through several cycles
including the closed position. Ensuring proper
operation and freedom of movement. Return
the actuator arm to the closed position.
Ignitor Rod
Hood
MILLIVOLT
Thermocouple
Step7.INSTALLINGLOGS,VERMICULITE,
DECORATIVE VOLCANIC STONE AND
GLOWING EMBERS
³⁄₈" Min
(9 mm)
Pilot
Nozzels
The log set is located within the firebox. One
plastic bag of glowing embers, one plastic bag
of decorative volcanic stone and one bag of
vermiculate, is located in the bottom compart-
ment. Refer to the Log Placement Guide for
detailed placement instructions for the log set
and glowing embers. See the Homeowners
Manual for placement instructions of vermicu-
late, decorative volcanic stone and rockwool.
Thermopile
Figure 22
Glass
Enclosure
Panel
Electronic Appliance Checkout
Bottom Vee-flanges
Latch
To light the burner, turn ‘ON’ the modesty
panelmountedON/OFFswitch andturnthegas
control switch to the “ON” position. Ensure the
ignitor lights the pilot. The pilot flame should
engulf the flame rod as shown in Figure 23.
Firebox
Floor
(Glass Enclosure
Panel Frame)
EBVST SHOWN
Figure 24 -
Step 8. CHECKINGAPPLIANCEOPERATION
Installing the Glass Enclosure Panel
ELECTRONIC
With gas line installed run initial system check-
out before closing up the front of the unit.
Follow the pilot lighting instructions provided
in the Homeowner's Care and Operation In-
structions.ForpiezoignitorlocationseeFigure
20 on page 12 (millivolt appliances only).
3/8 To 1/2 Inch
Proper Flame
(9 mm to 13 mm)
Adjustment
WARNING: HANDLE THE GLASS WITH
EXTREME CARE! TEMPERED GLASS IS
SUSCEPTIBLETODAMAGE(SCRATCHES,
FOR EXAMPLE) – HANDLE GLASS DOOR
(GLASS ENCLOSURE PANEL) GENTLY
WHILE REINSTALLING IT.
Pilot
Nozzle
Ground
Electrode
Note: Lighting instructions may also be found
on the pull out lighting instruction labels
attached to the gas control valve.
Flame Rod
Hot Surface
Igniter
WARNING: NEVER OPERATE THE APPLI-
ANCE WITHOUT THE FRONT GLASS EN-
CLOSURE PANEL IN PLACE AND SECURE.
To access the label, see the procedure on the
previous page described for accessing the gas
control valve.
Figure 23
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Step 10. BURNER ADJUSTMENTS
Manually-Reset Safety Limit Switch
This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to Figure 26
for its location. If, during appliance operation, the flame goes out (independently of the burner on/
off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance
to cool, then reset the safety switch by pushing the red reset button on the back of the switch.
Note - The air shutter for the burner primary air
openingisfactory-set. Donotadjustthefactory-
setposition. Thefactory-setpositionisshownin
Figure 25.
To access the blocked flue safety limit switch refer to Figure 26:
*Air Shutter
Opening
Burner
Venturi
Tube
A - To access the blocked flue safety switch when top radiant panel is not covered with non-
combustible material:
1 - Lift up and remove top radiant panel/eyebrow assembly on the control side of unit.
2 - Reach between the cabinet side and the firebox side wall and locate the blocked flue safety
switch.
Orifice
3 - Push the red reset button on the switch.
The applilance should then relight and remain lit. If this does not occur, turn off the appliance and
call a qualified service technician.
Millivolt Shown
B - To access the blocked flue safety switch when top radiant panel is covered with non-
combustible material:
*Note - Do Not Adjust the Factory-Set Position.
Theshutteropeningisshowninthetable
below.
NOTE - This procedure should only be performed by a qualified service technician.
Important - Turn electrical power off before beginning this procedure.
MAIN BURNER
FACTORY SHUTTER SETTING
1 - Lower bottom hinged panel on the control side of the fireplace. Remove the modesty panel
and glass enclosure panel as described on page 5, Steps 3, 4, 5 and 6 under "Detailed Installation
Steps" heading.
2 - Remove the side baffle securing screws (5) and then remove the baffle.
3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly
through the side panel slot.
4 - Push the red reset button on the switch.
5 - Reinstall the switch/bracket assembly.
6 - Reinstall the side baffle.
Propane
Gas
inches
(mm)
Natural Gas
inches
(mm)
Models
EBVST
EBVPF
EBVCR
EBVCL
1/16 (1.5)
7/16 (11)
7 - Reinstall front glass door.
8 - Raise the bottom hinged panel.
Figure 25
The appliance should then relight and remain lit. If this does not occur, check unit for a blocked
flue condition.
Step 11. Spillage Test and Safety Limit
Switch Operation
Spillage Test
SAFETY SWITCH LOCATION (EBVCL SHOWN) EBVST and EBVPF Safety Switch Location Also as Shown;
EBVCR Location on the Left End of the Fireplace.
After appliance installation, perform this spillage
test to verify that proper venting conditions exist:
1 - Place unit in its normally-operated con-
dition, that is, with the glass enclosure pan-
els in place.
FIREBOX SIDE BAFFLE SECURING SCREW
FIREBOX SIDE BAFFLE
MANUALLY-RESET
2 - Close all doors and windows in the
room. Turn on all exhaust fans in the house.
3 - Light the appliance.
SAFETY LIMIT SWITCH
FIREBOX
SIDE WALL
4 - Wait 15 minutes.
5 - To check for venting action, start by
holding a smoke producing device within an
inch of one edge (side edge, not top or
bottom edge) of one glass enclosure panel.
The smoke should be drawn toward the edge
of the glass enclosure panel. Continue the
test by moving the smoke producing device
along the entire length of both side-edges of
the glass door. Repeat the test for all glass
enclosure panels.
TOP RADIANT PANEL
AND EYEBROW
BRACKET
SECURING SCREW
SAFETY SWITCH
6 - If the smoke is not drawn towards the
edges of the glass door turn off the appli-
anceandcallaqualifiedservicetechnican.
CABINET
SIDE WALL
Figure 26
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
14
Step 12. HOOD INSTALLATION
COLD CLIMATE INSULATION
All of these appliances must have hoods installed prior to operating on all sides with glass
enclosure panels.
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter the
room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other open-
ings should be caulked or stuffed with unfaced
fiberglass insulation. In cold climates, if the
fireplace is being installed on a cement slab, a
sheet of plywood or other raised platform can
be placed underneath to prevent conducting
coldupintotheroom. Italsohelpstosheetrock
inside surfaces and tape for maximum air
tightness and caulk firestops.
On all clean face units, slide the hoods into the slots on the lower edges of the radiant panels (Figure 28).
FINISHING REQUIREMENTS
Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position
framework to accommodate the thickness of the finished wall (Figures 28 ).
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the
control compartment access panel. Any hearth extension used is for appearance only and does not
have to conform to standard hearth extension installation requirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to
encroach the area defined by the appliance front face (black sheet metal). Never allow
combustible materials to be positioned in front of or overlapping the appliance front face.
See Figures 28.
Combustible Wall
This Area Must Remain Clear
of Combustible Materials
Framing
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance
frontfacewiththeseexceptions:theymustnotcoveranyportionof theglass or louvers; they mustnotcover
any portion of the top radiant panel and the air gaps surrounding the top radiant panel.
1" Min
(25 mm)
Combustible
Wall Framing
Spacer
Vertical installation clearances to combustible mantels vary according to the depth of the mantel.
(See Figure 27). Mantels constructed of non-combustible materials may be installed at any height
above the appliance opening; however, do not allow anything to hang below the hood.
Combustible
Finished Wall
Materials May
Top of Appliance
Touch Top of
MANTEL CLEARANCES
Inches (mm)
Unit
Radiant panel
Top of Door Frame
12 (305) MANTEL
Hood must be installed as shown.
Clean Face Models
10 (254) MANTEL
8 (203) MANTEL
Figure 28
6 (152) MANTEL
14
12
(356)
4 (102) MANTEL
2 (51) MANTEL
(305)
10
(254)
TOP OF
APPLIANCE
8
6
(203)
(152)
4
(102)
NOTE - Hood shown as positioned
in louvered front model. The hood
position in the flush faced front model
is lower than shown.
*Note - The side walls of mantels may protrude
beyond the front face of the fireplace a maximum
of 5 inches (127mm) at 0 inch clearance to the
sides of the fireplace.
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
GAS CONVERSION KITS
WARNING: THIS CONVERSION KIT SHALL BE
INSTALLED BY A QUALIFIED SERVICE AGENCY IN
ACCORDANCE WITH THE MANUFACTURER'S IN-
STRUCTIONS AND ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AUTHORIZED AGENCY
HAVING JURISDICTION. IF THE INFORMATION IN
THESE INSTRUCTIONS IS NOT FOLLOWED EX-
ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF
CARBON MONOXIDE MAY RESULT CAUSING
PROPERTYDAMAGE,PERSONALINJURYORLOSS
OFLIFE. THEINSTALLATIONISNOTPROPERAND
COMPLETE UNTIL THE OPERATION OF THE CON-
VERTEDAPPLIANCEISCHECKEDASSPECIFIEDIN
THEOWNERINSTRUCTIONSSUPPLIEDWITHTHE
KIT.THEQUALIFIEDSERVICEAGENCYPERFORM-
ING THIS INSTALLATION ASSUMES RESPONSI-
BILITY FOR THIS CONVERSION.
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SER-
VICE CONFORMÉMENT AUX INSTRUCTIONS DU
FABRICANT ET TOUTES EXIGENCES ET CODES
APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION.
SI L'INFORMATION DANS CETTE INSTRUCTION N'EST
PASSUIVIEEXACTEMENT,UNFEU,EXPLOSIONOUPRO-
DUCTIONDEPROTOXYDEDECARBONEPEUTRÉSULTER
LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU
BLESSUREPERSONNELLEDEVIE. L'AGENCEQUALIFIÉE
DE SERVICE EST ESPONSABLE DE L'INSTALLATION
PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST
PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE
L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES
CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE
PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
In Canada:
b. Remove the bottom control compartment
Natural To Propane Gas Conversion Kit
THE CONVERSION SHALL BE CARRIED OUT
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN1-B149.1
AND .2 INSTALLATION CODE.
access panel by compressing the spring-
loaded hinge pin on the left side until it
disengages from the left cabinet panel
hole. Pull the panel away from the fire-
place. See Figure 20 on page 12.
Models No. Unit Type
Catalog No.
H2198
millivolt
EBVST
EBVPF
electronic
H2200
c. Remove the modesty panel by pulling the
bottom right corner of the modesty panel
out slightly to disengage the snap-fit fea-
ture; lift the modesty panel by the tab on
the panel's right end, pull the right end of
the panel away from the cabinet and then
pull the panel diagonally out of the left side
cabinet panel slots. (In the above proce-
dure, reverse the words "left" and "right"
for EBVCR models). Remove the modesty
panel carefully, so that none of the wires
become loose or disconnected.
d. Locate the latch at the top of the control
compartment.Todisengagethelatchfrom
the bottom vee-flange of the glass enclo-
sure panel, reach for the handles located
towards the back of the latch and pull the
handl down toward the front of the unit.
e. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door
frame away from the appliance.
Natural To Propane Gas Conversion Kit
LA CONVERSION DEVRA ÊTRE EFFECTUÉE
CONFORMÉMENTAUXRECOMMANDATIONS
DES AUTORITÉS PROVINCIALES AYANT
JURIDICTION ET CONFORMÉMENT AUX
EXIGENCESDUCODED'INSTALLATIONCAN1-
B149.1 ET.2.
Models No. Unit Type
Catalog No.
H2198
millivolt
EBVCR
EBVCL
electronic
H2200
Propane to Natural Gas Conversion Kit
Gas conversion kits are available to convert
your appliance from the use of one type of gas
to the use of another. These kits contain all the
necessary components needed to complete
the task including labeling that must be affixed
to ensure safe operation.
Model No.
Unit Type
millivolt
Catalog No.
H2199
EBVST
EBVPF
electronic
H2201
Propane to Natural Gas Conversion Kit
Kitpartnumbersarelistedhereandthefollow-
ing steps detail the conversion procedure.
Model No.
Unit Type
millivolt
Catalog No.
H2203
Step 1. Turn off the gas supply to the appliance.
a. Openthecontrolcompartmentaccesspanel,
by actuating the spring-loaded magnetic
catches securing the panel, gently depress-
ingtheoutertopcornersofthepaneluntilthe
catches"pop"thepanelfreeandallowingitto
swing out and down to open.
EBVCR
EBVCL
electronic
H2205
Step 2. Carefully remove the logs. Exercise
care as not to break the logs.
Step 3. Referring to Figure 29 on page 17,
remove the burner.
16
PAN BURNER
Inlet Pressure Test Port
Pressure
Regulator
Manifold
Pressure
Test Port
Remove
These
Components
Slotted
Cap
FIREBOX BOTTOM
BACK OF FIREPLACE
Spring
Figure 30
Adjusting
Screw
Step 6. Refer to Figure 31 and remove the
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with
the one provided with the kit.
BURNER POSITIONING
Figure 32
PAN
BURNER
See Figure 33 and replace the pilot orifice as
follows: Remove the ignitor assembly retainer
clip, andcarefullyremovetheignitorassembly.
Exercise extreme care to prevent damage to
or breakage of the ignitor assembly. Remove
the screw securing the pilot assembly to its
mounting bracket. Back off the flare nut at the
end of the pilot gas line to free the pilot assem-
bly from the gas line. Remove the pilot orifice
and replace it with the one provided with the
conversion kit. Reinstall the pilot assembly by
reversing the steps detailed here.
PILOT ASSEMBLY
Pilot
Orifice
Figure 29
When reinstalling the ignitor assembly, use
extreme care to prevent damage and break-
age. Do not apply any leverage to the ignitor
assembly while restoring the retainer clip to
its original position.
Figure 31
Millivolt Appliances
Electronic Appliances
Step 4. SIT Systems - Refer to Figure 30 and
the instructions provided with the kit. Using a
Torx T20, remove and discard the three pres-
sure regulator mounting screws. Remove the
pressure regulator, spring, poppet, diaphragm
and bushing. Discard all removed compo-
nents. Ensure the rubber gasket installed on
the back of the replacement pressure regulator
is properly positioned and install the new pres-
sure regulator using the new screws supplied
with the kit. Tighten screws to 25 In. lb. torque.
Step 7. Honeywell Electronic Valves - See
Figure 32 and the instructions provided with
the kit. Remove the slotted cap screw, o-ring,
pressure-regulating adjusting screw and
spring. Retain all parts for possible later use.
Install new components from the kit. Black
cap and red spring for propane gas units.
Silvercapandstainlesssteelspringfronatural
gas units.
Pilot
Assembly
Pilot
Orifice
Ignitor
Assembly
Before installing the cap, attach manometer
to the manifold side pressure test fitting and
adjust screw until pressure reads 3.5 inches
water column (0.87 kPa) for natural gas, and
10.0 inches water column (2.49 kPa) for
propane gas.
Step5.Attachmanometertothemanifoldside
pressure test fitting and verify manifold pres-
sure reads 3.5 inches water column (0.87 kPa)
for natural gas, and 10.0 inches water column
(2.49 kPa) for propane gas.
Retaining
Clip
Flare Nut
Note: If the ignitor is damaged, a replace-
ment kit is available, order Catalog Number
87L54.
Figure 33
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
All Models
Step 9. Reassemble the remaining compo-
nents by reversing the procedures outlined in
the preceding steps. Use pipe joint compound
or Teflon tape on all pipe fittings before install-
ing (ensure propane resistant compounds are
used in propane applications, do not use pipe
joint compounds on flare fittings).
Kit Catalog No.
H2199 and H2201
Step 8. (Refer to Figure 29 )
THIS APPLIANCE HAS BEEN CONVERTED TO:
NATURAL GAS
A. Remove the orifice from the manifold
andreplaceitwiththeoneprovidedinthe
kit. See the following table for orifice
sizes for natural and propane models.
Figure 34 illustrates the orifice.
INPUT BTU/HR
MANIFOLD PRESSURE
ORIFICE SIZE #32
–
37,500
–
3.5"
–
Step 10. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance. Figure 35 shows all of the labels for
all of the kits covered by this manual as shown
in the tables on page 17. Compare the label
provided in the kit being installed to the appro-
priate label shown in Figure 35.
Kit Catalog No.
H2203 and H2205
B. InstalltheburnersasshowninFigure29.
The primary air opening can be adjusted
by removing the venturi tube air shutter
securing screw and placing it in the other
hole provided nearby. The correct hole
usage for this screw for the gas being
used can be determined by the air shutter
gap indicated in Figure 25 on page 14.
THIS APPLIANCE HAS BEEN CONVERTED TO:
NATURAL GAS
INPUT BTU/HR
MANIFOLD PRESSURE
ORIFICE SIZE #34
–
34,000
–
3.5"
–
Step 11. Turn on the gas supply and test for
leaks as shown in step 5 on page 11.
Kit Catalog No.
H2198 and H2200
Elevation
Feet
(meters)
Orifice size
Model
No.
THIS APPLIANCE HAS BEEN CONVERTED TO:
Nat. Prop.
PROPANE/LPG
EBVST
EBVPF
INPUT BTU/HR
MANIFOLD PRESSURE
ORIFICE SIZE #50
–
34,000
#32
#34
#50
#50
–
10.0"
0-4500
(0-1372)
–
EBVCR
EBVCL
Figure 35
Figure 34
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
18
NOTES:
19
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2004 by LENNOX HEARTH PRODUCTS
P/N 850,025M REV. B 01/2007
1110 West Taft Avenue • Orange, CA 92865
|